Hardware Features
Compact Series Specifications
Operating Environment
Ambient operating environment
Ambient operating temperature
Ambient operating temperature
(extended temperature) option
Relative Humidity
Shipping and storage environment
Mounting Surface
Vibration
Protection to EN60529
Agency Listings
UL
Agency Compliance
OSHPD Seismic Certification
BTL
32 | 100
Siemens Industry, Inc.
Building Technologies
Operate in a dry location, which is protected from exposure to salt spray or other corrosive
with rooftop
PXC-16 and PXC-24: Direct equipment mount, building wall, or structural member
Requires installation inside a NEMA-4 rated enclosure, or a similarly-protected
Product meets OSHPD Special Seismic Preapproval certification (OSH-0217-10) under California
Building Code 2010 (CBC2010) and International Building Code 2009 (IBC2009) when installed
within the following Siemens enclosure part numbers: PXA-ENC18, PXA-ENC19, or PXA-ENC34.
BACnet Testing Laboratories (BTL) Certified, Firmware Revision 3.0 and later
Technical Reference Manual
elements. Exposure to flammable or explosive vapors must be prevented.
PXC-16 and PXC-24: 5 to 95% rh non-condensing
PXC-16 and PXC-24: -40°F to 185°F (-40°C to 85°C)
Must be installed inside a metal enclosure rated at IP20 minimum
Requires installation inside a PX series enclosure
Compliance to IEC 60721, Class 2M2 and 3M2
UL864 UUKL Smoke Control Equipment (except UEC and rooftop models)
UL864 UUKL7 Smoke Control Equipment (except UEC and rooftop models)
FCC Compliance CFR47 Part 15, Subpart B, Class B
Restricted
32°F to 122°F (0°C to 50°C)
-40°F to 158°F (-40°C to 70°C)
PXC-36: 5 to 95% rh non-condensing
PXC-36: -13°F to 158°F (-25°C to 70°C)
PXC-36: Building wall or a secure structure
CE Compliance
Smoke Control Applications
Outdoor Applications
CAN/ULC-S527-M8 (except rooftop models)
UL916 PAZX (all models)
UL916 PAZX7 (all models)
Australian EMC Framework
European EMC Directive (CE)
European Low Voltage Directive (LVD)
RoHS Compliant
environment
IP 20