Hoa Specifications; Hardware Features; Default Mapping - Siemens PXC-16 Compact Technical Reference Manual

Table of Contents

Advertisement

Hardware Features

HOA (Hand-Off-Auto) Upgrade Kits
Electrical
Power Consumption
Baud rate
Dimensions (L x W x D)
Weight
8 Switch
16 Switch
Operating Environment
Ambient Operating Temperature
Ambient Operating Temperature for rooftop (extended
temperature model)
Shipping and Storage
Agency Listings
UL Listing
cUL Listed
FCC Compliance
WEEE
RoHS
40 | 100
Siemens Industry, Inc.
Building Technologies

HOA Specifications

Hardware Features
HOA switches enable points to be manually placed into HAND, ON/OFF, or AUTO
control. Analog outputs can also be placed into AUTO and ten manual control
positions.
Serial communication is made by either direct connect or through the use of a serial
HMI cable.

Default Mapping

For each type of PXC Compact (16, 24 and 36) that supports HOA and each HOA unit
(8, 16 rooftop or 16 non-rooftop UL 864), there is a default mapping between each
button and physical point.
The default mapping provides Plug-and-Play functionality. Upon connection of the
HOA Upgrade Kit to the host field panel, the HOA device is recognized and its
switches are automatically assigned to the controllers fixed digital output and fixed
analog output points. The default mapping is also used to allow the HOA board to
command physical outputs before any logical points have been defined.
Technical Reference Manual
CAN/ULC-S527-M8 (except rooftop model)
Canadian Standards C22.2 No. 205-M1983, PAZX7
Restricted
5 V/60 mA
(from host controller)
5.65 in. × 1.8 in. × 0.68 in.
(14.4 cm × 4.6 cm × 1.7 cm)
23°F to 122°F (-5°C to 50°C)
-40°F to 158°F (-40°C to 70°C)
-13°F to 167°F(-25°C to 70°C)
UL864 UUKL (except rooftop model)
UL864 UUKL7 (except rooftop model)
UL 916 PAZX (all models)
47 CFR Part 15
38400
0.12 lb
0.14 lb
145-172
2018-09-25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents