Siemens PXC-16 Compact Technical Reference Manual page 13

Table of Contents

Advertisement

Point Type
Analog
Voltage 0 to 10 Vdc
Output
Current 0 to 20 mA
Digital
Binary/Digital Output
Output
Platinum 1K 375 or 385 alpha.
1)
Siemens, Johnson Controls, and DIN Standard Nickel.
2)
10K and 100K Type 2 and 10K Type 3.
3)
Requires an external relay.
4)
Sensor supply 24 Vdc, 4.8W
5)
Point Type
Analog Input
Voltage 0 to 10 Vdc
5
Current 4 to 20 mA
RTD Pt 1K
1
RTD Ni 1K
2
Thermistor 10K NTC
Thermistor 100K NTC
Digital Input
Status (Binary Input)
Pulse Accumulator (Counter)
Analog
Voltage 0 to 10 Vdc
Output
Current 0 to 20 mA
Digital
Binary/Digital Output
Output
Platinum 1K 375 or 385 alpha.
1)
Siemens, Johnson Controls, and DIN Standard Nickel.
2)
10K and 100K Type 2 and 10K Type 3.
3)
Requires an external relay.
4)
Sensor supply 24 Vdc, 4.8W
5)
Siemens Industry, Inc.
Building Technologies
PXC-24 Supported Point Types.
Configurable Points
Universal
Universal
Input (UI)
Input/Output (U)
Points 1-3
Points 4-12
PXC-36 Supported Point Types.
Configurable Points
Super Universal
(X)
Points 1-6
3
3
4
Technical Reference Manual
Restricted
Compact Series Product Overview
Super Universal (X)
Analog Output
Points 13-16
(AO)
Points 17-19
4
Universal
Digital Input (DI)
Input/Output (U)
Points 25-28
Points 7-24
Supported Point Types
Dedicated Points
Digital Output
(DO)
Points 20-24
Dedicated Points
Digital Output (DO)
Points 29-36
13 | 100