Emerson Rosemount 3101 Quick Start Manual page 13

Ultrasonic liquid level transmitters
Hide thumbs Also See for Rosemount 3101:
Table of Contents

Advertisement

September 2018
When setting the bottom reference on a 'V'- notch weir
important the true invert is used and not the meniscus level.
Figure 10. Bottom Reference of 'V'-notch Weir
A. Transmitter bottom reference (i.e. true invert)
Note
The transmitter should be free from a situation where it is likely to 'drown'
(refer to the relevant standard for further information).
If the flow structure permits, mount the transmitter within the flow channel
or chamber. Shroud the transmitter from direct sunlight for maximum
accuracy and stability.
The Rosemount 3102 and Rosemount 3105 have the option of a Remote
Temperature Sensor (RTS). This temperature sensor should be mounted in a
location where it can get an accurate air temperature measurement and is
protected from sunlight. (See
installation information).
A
B
Quick Installation Guide
Quick Start Guide
(Figure
10), it is
b. Meniscus level
for further RTS
13