Verify Configuration - Emerson Rosemount 3051SF Series Quick Start Manual

Pressure transmitter and flowmeter with hart protocol
Hide thumbs Also See for Rosemount 3051SF Series:

Advertisement

Quick Start Guide
5

Verify configuration

Use any HART-compliant master to communicate with and verify
configuration of the Rosemount 3051S.
Field Communicator user interface
Fast Key sequences vary with the device driver revision. Reference
for DD Rev. 8 or older. Reference
Figure 5-1: Traditional Interface - Device Revision 6 or 7 and DD Revision 7
Figure 5-2: Device Dashboard - Device Revision 7 and DD Revision 9
A check (✓) indicates the basic configuration parameters. At a minimum,
these parameters should be verified as part of the configuration and startup
procedure.
Table 5-1: Fast Key Sequences-Traditional Interface (Device Revision 6 or
7 and DD Revision 7)
22
Table 5-2
3051:PT 93207
Online
1 Device setup
2 PV
3 Analog Output
4 PV LRV
5 PV URV
SAVE
3051:PT 93207
Online
1 Overview
2 Configure
3 Service Tools
SAVE
Function
Alarm Level Configuration
Alarm and Saturation
Levels
for DD Rev. 9 or newer.
0.00 mbar
4.000 mA
0.00 mbar
370.00 mbar
Fast Key sequence
1, 4, 2, 7, 7
1, 4, 2, 7
December 2018
Table 5-1
Rosemount 3051S