Quick Guide
1
1
1.3.2 Side-by-Side Installation
The frequency converter can be mounted side-by-side and
requires the clearance above and below for cooling, as
stated in Table 1.4.
Frame
IP class
H1
IP20
H2
IP20
H3
IP20
H4
IP20
H5
IP20
H6
IP20
H7
IP20
H8
IP20
Table 1.4
NOTE
With IP21/Nema Type1 option kit mounted, a distance of
50 mm between the units is required.
4
®
VLT
HVAC Basic Drive Cascade Controller Quick Guide
Power
Clearance
above/below
[mm/inch]
3x380-480 V
0.37-1.5 kW/
100/4
0.5-2 hp
2.2-4 kW/
100/4
3-5.4 hp
5.5-7.5 kW/
100/4
7.5-10 hp
11-15 kW/
100/4
15-20 hp
18.5-22 kW/
100/4
25-30 hp
30-45 kW/
200/7.9
40-60 hp
55-75 kW/
200/7.9
100-120 hp
90 kW/
225/8.9
125 hp
MG18F402 - VLT
®
is a registered Danfoss trademark