Special Conditions; Derating For Ambient Temperature And Switching Frequency; Derating For Low Air Pressure - Danfoss VLT Series Quick Manual

Hvac basic drive cascade controller
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

®
Quick Guide
VLT
HVAC Basic Drive Cascade Controller Quick Guide
1
1
Derating for high altitude, see 1.9 Special Conditions
Safety standards
EN/IEC 61800-5-1, UL 508C
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN
EMC standards, Immunity
61000-4-5, EN 61000-4-6

1.9 Special Conditions

1.9.1 Derating for Ambient Temperature
and Switching Frequency
The ambient temperature measured over 24 hours should
be at least 5 °C lower than the max. ambient temperature.
If the frequency converter is operated at high ambient
temperature, the continuous output current should be
®
decreased. For derating curve, see VLT
HVAC Basic Design
Guide.

1.9.2 Derating for Low Air Pressure

The cooling capability of air is decreased at low air
pressure. For altitudes above 2000 m, contact Danfoss
regarding PELV. Below 1000 m altitude no de-rating is
necessary, but above 1000 m the ambient temperature or
the maximum output current should be decreased.
Decrease the output by 1% per 100 m altitude above 1000
m or reduce the max. ambient temperature by 1° per 200
m.
®
34
MG18F402 - VLT
is a registered Danfoss trademark

Advertisement

Table of Contents
loading

Table of Contents