Danfoss VLT Series Quick Manual page 17

Hvac basic drive cascade controller
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

Quick Guide
Parameter
Range
0-03 Regional Settings
[0] International
[1] US
0-06 GridType
[0] 200-240 V/50 Hz/IT-grid
[1] 200-240 V/50 Hz/Delta
[2] 200-240 V/50 Hz
[10] 380-440 V/50 Hz/IT-grid
[11] 380-440 V/50 Hz/Delta
[12] 380-440 V/50 Hz
[20] 440-480 V/50 Hz/IT-grid
[21] 440-480 V/50 Hz/Delta
[22] 440-480 V/50 Hz
[30] 525-600 V/50 Hz/IT-grid
[31] 525-600 V/50 Hz/Delta
[32] 525-600 V/50 Hz
[100] 200-240 V/60 Hz/IT-grid
[101] 200-240 V/60 Hz/Delta
[102] 200-240 V/60 Hz
[110] 380-440 V/60 Hz/IT-grid
[111] 380-440 V/60 Hz/Delta
[112] 380-440 V/60 Hz
[120] 440-480 V/60 Hz/IT-grid
[121] 440-480 V/60 Hz/Delta
[122] 440-480 V/60 Hz
[130] 525-600 V/60 Hz/IT-grid
[131] 525-600 V/60 Hz/Delta
[132] 525-600 V/60 Hz
1-20 Motor Power
0.12-110 kW/0.16-150 hp
1-22 Motor Voltage
50.0-1000.0 V
1-23 Motor Frequency
20.0-400.0 Hz
1-24 Motor Current
0.01-10000.00 A
1-25 Motor Nominal
100.0-9999.0 RPM
Speed
1-26 Torque nominal do
0.1-1000.0
Motor
1-29 Automatic Motor
See 1-29 Automatic Motor
Adaption (AMA)
Adaption (AMA)
1-30 Resistência do
0.000-99.990
Estator (Rs)
1-37 Indutância do eixo-d
0-1000
(Ld)
1-39 Pólos do Motor
2-100
1-40 Força Contra Eletro-
10-9000
motriz em 1000RPM
1-73 Flying Start
®
VLT
HVAC Basic Drive Cascade Controller Quick Guide
Default
0
Size related
Size related
Size related
Size related
Size related
Size related
Size related
Off
Size related
Size related
4
Size related
®
MG18F402 - VLT
is a registered Danfoss trademark
Function
Select operating mode for restart upon
reconnection of the drive to mains voltage after
power down.
Enter motor power from nameplate data.
Enter motor voltage from nameplate data.
Enter motor frequency from nameplate data.
Enter motor current from nameplate data.
Enter motor nominal speed from nameplate data
This parameter is available only when
1-10 Construção do Motor Design is set to [1] PM,
non-salient SPM .
NOTE
Changing this parameter will affect settings
of other parameters.
Performing an AMA optimizes motor performance.
Set the stator resistance value.
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance cannot
be found by performing an AMA.
Enter the number of motor poles.
Line-Line RMS back EMF voltage at 1000 RPM.
When PM is selected, Flying Start is enabled and
can not disable.
1
1
15