Danfoss VLT Series Quick Manual page 18

Hvac basic drive cascade controller
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

Quick Guide
1
1
Parameter
1-73 Flying Start
3-02 Minimum Reference -4999-4999
3-03 Maximum Reference -4999-4999
3-41 Ramp 1 Ramp Up
Time
3-42 Ramp 1 Ramp
Down Time
4-12 Motor Speed Low
Limit [Hz]
4-14 Motor Speed High
Limit [Hz]
4-19 Freqüência Máx. de
Saída
5-40 Function Relay [0]
Function relay
5-40 Function Relay [1]
Function relay
6-10 Terminal 53 Low
Voltage
6-11 Terminal 53 High
Voltage
6-12 Terminal 53 Low
Current
6-13 Terminal 53 High
Current
6-19 Terminal 53 mode
Table 1.17 The Start-up Wizard for Open Loop Applications
16
®
VLT
HVAC Basic Drive Cascade Controller Quick Guide
Range
[0] Disabled
[1] Enabled
0.05-3600.0 s
0.05-3600.0 s
0.0-400 Hz
0.0-400 Hz
0-400
See 5-40 Function Relay
See 5-40 Function Relay
0-10 V
0-10 V
0-20 mA
0-20 mA
[0] Current
[1] Voltage
MG18F402 - VLT
Default
Function
0
Select [1] Enable to enable the drive to catch a
motor spinning due to mains drop-out. Select [0]
Disable if this function is not required. When is
enabled 1-71 Start Delay and 1-72 Função de
Partida have no function. is active in VVC
only
0
The minimum reference is the lowest value
obtainable by summing all references.
50
The maximum reference is the lowest obtainable
by summing all references.
Size related
Ramp up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected; ramp up
time from 0 to 1-25 Motor Nominal Speed if PM
motor is selected.
Size related
Ramp down time from rated 1-23 Motor
Frequency to 0 if Asynchron motor is selected;
ramp down time from 1-25 Motor Nominal Speed
to 0 if PM motor is selected.
0 Hz
Enter the minimum limit for low speed.
65 Hz
Enter the maximum limit for high speed.
Size related
Enter the maximum output frequency value.
Alarm
Select the function to control output relay 1.
Drive running
Select the function to control output relay 2.
0.07 V
Enter the voltage that corresponds to the low
reference value.
10 V
Enter the voltage that corresponds to the high
reference value.
4
Enter the current that corresponds to the low
reference value.
20
Enter the current that corresponds to the high
reference value.
1
Select if terminal 53 is used for current- or voltage
input.
®