Danfoss VLT Series Quick Manual page 30

Hvac basic drive cascade controller
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

Quick Guide
1
1
Alarm/
Warning
Fault
number
Number
54
55
56
57
58
59
60
66
69
79
80
87
95
200
202
250
251
Table 1.22
28
Bit
Fault text
Warning Alarm
AMA small
mot
AMA par.
range
AMA user
interrupt
AMA timeout
AMA internal
X
25
Current limit
X
External
44
Interlock
Heat sink
Temperature
26
Low
X
Pwr. Card
1
Temp
X
Illegal power
section config-
uration
X
Drive
29
initialised
Auto DC
47
Braking
X
40
Broken Belt
X
Fire Mode
X
Fire Mode
Limits
Exceeded
X
New sparepart
New Typecode
MG18F402 - VLT
®
VLT
HVAC Basic Drive Cascade Controller Quick Guide
Trip
locked Cause of problem
X
The motor is too small for the AMA to be carried out.
The parameter values found from the motor are outside
X
acceptable range.
X
The AMA has been interrupted by the user.
Try to start the AMA again a number of times, until the AMA is
carried out.
NOTE
Repeated runs may heat the motor to a level where the
resistance Rs and Rr are increased. In most cases, however,
this is not critical.
X
X
Contact your local Danfoss supplier.
The current is higher than the value in 4-18 Current Limit.
External interlock has been activated. To resume normal operation,
apply 24 V DC to the terminal programmed for external interlock
and reset the frequency converter (via serial communication,
X
digital I/O, or by pressing [Reset]).
This warning is based on the temperature sensor in the IGBT
module (Only on 400 V 30-90 kW units).
The temperature sensor on the power card is either too hot or too
X
X
cold.
X
Internal fault. Contact your local Danfoss supplier.
X
All parameter settings are initialized to default settings.
The frequency converter is auto DC braking.
Torque is below the torque level set for no load, indicating a
X
broken belt. See parameter group 22-6* Broken Belt Detection.
Fire mode has been activated
Fire Mode has suppressed one or more warranty voiding alarms.
The power or switch mode power supply has been exchanged.
(Only on 400 V 30-90 kW units). Contact your local Danfoss
X
X
supplier.
The frequency converter has a new type code (only on 400 V,
X
X
30-90 kW units). Contact your local Danfoss supplier.
®