Danfoss VLT Series Quick Manual page 35

Hvac basic drive cascade controller
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

Quick Guide
Digital output
Number of digital outputs
Terminal number
Voltage level at digital output (output current=20 mA)
Max Voltage level at digital output (output current <4 mA)
Max. output current
1)
Terminals 42 and 45 can also be programmed as analog outputs.
Control card, RS-485 serial communication
Terminal number
Terminal number
Control card, 24 V DC output
Terminal number
Max. load enclosure frame H1-H8, I2-I8
Relay output
A)
Programmable relay output
Relay 01 and 02
Max. terminal load (AC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
1)
Max. terminal load (AC-15)
on 01-02/04-05 (NO) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 01-02/04-05 (NO) (Resistive load)
Max. terminal load (DC-13)
1)
on 01-02/04-05 (NO) (Inductive load)
Max. terminal load (AC-1)
1)
on 01-03/04-06 (NC) (Resistive load)
1)
Max. terminal load (AC-15)
on 01-03/04-06 (NC) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 01-03/04-06
(NC) (Resistive load)
Environment according to EN 60664-1
1)
IEC 60947 parts 4 and 5.
A)
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
A)
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
Surroundings
Enclosure
Enclosure kit available
Vibration test
Max. relative humidity
Aggressive environment (IEC 60721-3-3), coated (standard) frame H1-H5
Aggressive environment (IEC 60721-3-3), non-coated frame H6-H10
Aggressive environment (IEC 60721-3-3), coated (optional) frame H6-H10
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Derating for high ambient temperature, see 1.9 Special Conditions.
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance, enclosure frame H1-H5
Minimum ambient temperature at reduced performance, enclosure frame H6-H10
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
®
VLT
HVAC Basic Drive Cascade Controller Quick Guide
A)
Min. terminal load on 01-03 (NC), 01-02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
5%-95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
See max. output current at 40/50 °C in 1.8.1 Mains Supply 3x380-480 V AC
®
MG18F402 - VLT
is a registered Danfoss trademark
68 (P, TX+, RX+), 69 (N, TX-, RX-)
61 Common for terminals 68 and 69
01-03 (NC), 01-02 (NO), 04-06 (NC), 04-05 (NO)
Overvoltage category III/pollution degree 2
1
2
1)
42, 45
12 V DC
17 V DC
20 mA
12
80 mA
2
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
24 V DC, 0.1 A
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
50
10.5 V ±0.5 V
25 mA
IP20
IP21, TYPE 1
1.0 g
Class 3C3
Class 3C2
Class 3C3
0 °C
-20 °C
-10 °C
-30 to +65/70 °C
1000 m
3000 m
33
1