How to operate numeric LCP (NLCP) Tips and tricks 6. How to program the adjustable frequency drive How to program Parameter list 0-** Operation and Display 1-** Load/Motor 2-** Brakes 3-** Reference/Ramps 4-** Limits/Warnings MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
20 motor overload protection, in accordance with NEC. • The ground leakage current exceeds 3.5 mA. • The [OFF] key is not a safety switch. It does not disconnect the adjustable frequency drive from the line power. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
The adjustable frequency drives also support other special applications, which affect the electrical ratings of the adjustable frequency drive. Special conditions that affect the electrical ratings might be: MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 5
□ Grid configuration (IT,TN, grounded leg, etc.) □ Safety of low voltage ports (PELV conditions). VLT® HVAC Drive Design Guide Consult the relevant clauses in these instructions and in the information about the installation requirements. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Be aware that there may be high voltage on the DC link even when the LEDs are turned off. 1.1.8. Installation at High Altitudes (PELV) At altitudes above 6,600 feet [2 km], please contact Danfoss Drives regarding PELV. 1.1.9. Avoid unintended Start.
Safe Stop function in accordance with the requirements of Safety Category 3 in EN 954-1, the related information and instructions of the VLT HVAC Drive Design Guide MG.11.BX.YY must be followed! The information and instructions contained in the Instruction Manual are not sufficient for a correct and safe use of the safe stop functionality! MG.11.A4.22 - VLT...
Par. 14-50 RFI 1 can be used to disconnect the internal RFI capacitors from the RFI filter to ground. If this is done, it will reduce the RFI performance to A2 level. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 9
1.1.12. Software Version and Approvals: VLT HVAC Drive VLT HVAC Drive Instruction Manual Software version: 2.0X This Instruction Manual can be used for all VLT HVAC Drive adjustable frequency drives with software version 2.0X. The software version number can be seen in parameter 15-43. 1.1.13. Disposal Instructions Equipment containing electrical components may not be disposed of together with domestic waste.
Page 10
2. Introduction ® HVAC Drive Instruction Manual MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
See table 2.1 for details of how to read theType code string (T/C). Illustration 2.1: This example shows an identification label. NOTE Please have T/C (type code) number and serial number ready before contacting Danfoss. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
XX: Standard software DX: No option D options 38-39 D0: DC backup Table 2.1: Type code description. VLT® HVAC Drive Design Guide, MG.11.Bx.yy The various options are described further in the MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 13
Rated Inverter Output Current Revolutions Per Minute Size Related Temperature ˚ C ˚ F Time s, hr Torque limit Velocity fps, fpm, fph Voltage Volume m³ in³, ft³ Table 2.2: Abbreviation and Standards table MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 14
3. Mechanical installation ® HVAC Drive Instruction Manual MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
5.5-11 18.5 - 30 37 - 45 200-240 V 7.5-10 1.1-4.0 1.1-7.5 11-18.5 22-30 37 - 55 75 - 90 380-480 V [5.5-7.5 1.1-4.0 5.5-7.5 525-600 V Table 3.1: Unpacking table MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 16
The packaging for these enclosures contains, as shown: Accessories bag (s), documentation and the unit. Depending on options fitted, there may be one or two bags and one or more booklets. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
[100 mm] free space above and below for cooling. With regard to ambient temperature ratings, Specifications Special Conditions please see the chapter , section Illustration 3.1: Side-by-side mounting of all frame sizes. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 18
Illustration 3.3: Other than A2 and A3 enclosures, do not mount units as shown without backplate. Cooling will be insufficient and service life can be drastically shortened. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 19
Illustration 3.6: Correct mounting of screws. Step 1: Drill according to the dimensions in the Step 2A: This way it is easy to hang the unit following table. on the screws. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 20
Illustration 3.8: Mounting of unit Step 2B: Do not tighten screws completely. Step 3: Lift the unit onto the screws. Illustration 3.9: Tightening of screws Step 4: Tighten the screws completely. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 21
® HVAC Drive Instruction Manual 3. Mechanical installation MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 22
Illustration 3.11: Correct mounting of screws Step 1: Drill according to the dimensions in the Step 2A: This way it is easy to hang the unit following table. on the screws. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 23
Step 2B: Do not tighten screws completely. Illustration 3.13: Mounting of unit. Step 3: Lift the unit onto the screws. Illustration 3.14: Tightening of screws Step 4: Tighten the screws completely. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 24
3. Mechanical installation ® HVAC Drive Instruction Manual MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 25
Table 3.4: A5, B1, B2, C1 and C2 mechanical dimensions. 1) The dimensions state the maximum height, width and depth needed for mounting the adjust- able frequency drive when the top cover is mounted. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 26
4. Electrical installation ® HVAC Drive Instruction Manual MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
The adjustable frequency drive must be protected against short circuit in order to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned in tables 4.3 and 4.4 in order to protect service personnel and equipment in case of an internal failure in the unit. The adjustable frequency drive provides full short circuit protection in case of a short circuit on the motor output.
Page 28
(symmetrical), 500 V / 600 V maximum. Non-UL compliance If UL/cUL is not to be complied with, Danfoss recommends using the fuses mentioned in table 4.2, which will ensure compliance with EN50178: In case of malfunction, not following the recommendation may result in unnecessary damage to the adjustable frequency drive.
Page 29
A6KR fuses from FERRAZ SHAWMUT may substitute for A2KR in 240 V adjustable fre- quency drives. A50X fuses from FERRAZ SHAWMUT may substitute for A25X in 240 V adjustable fre- quency drives. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
1.1-3.0 1.1-3.7 5.5-11 18.5-30 37-45 200-240 V 1.1-4.0 5.5-7.5 1.1-7.5 11-18.5 22-30 37-55 75-90 380-480 V 2.2-4.0 5.5-7.5 525-600 V Goto: 4.1.5 4.1.6 4.1.7 4.1.8 Table 4.5: Line power wiring table. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 31
Illustration 4.3: When mounting cables, first mount and tighten the ground cable. The ground connection cable cross-section must be at least 0.016 in [10 mm ] or EN 50178/IEC 2 rated line power wires terminated separately according to 61800-5-1 MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 32
4. Electrical installation ® HVAC Drive Instruction Manual Illustration 4.4: Then insert the line power plug and tighten the wires. Illustration 4.5: Finally, tighten the support bracket on the line power wires. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 33
Illustration 4.6: How to connect to line power and grounding without the line disconnect switch. Note that a cable clamp is used. Illustration 4.7: How to connect to line power and grounding with the line disconnect switch. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 34
4.1.7. Line power connection for B1 and B2. Illustration 4.8: How to connect to the line supply and grounding. 4.1.8. Line power connection for C1 and C2. Illustration 4.9: How to connect to the line supply and grounding. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Furthermore, the terminal screw must be retightened after two days due to the softness of the aluminum. It is crucial to ensure the connection makes a gas tight joint, otherwise the aluminum surface will oxidize again. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
1.1-3.0 1.1-3.7 5.5-11 18.5-30 37-45 200-240 V 1.1-4.0 5.5-7.5 1.1-7.5 11-18.5 22-30 37-55 75-90 380-480 V 2.2-4.0 5.5-7.5 525-600 V Goto: 4.1.11 4.1.12 4.1.13 4.1.14 Table 4.7: Motor wiring table. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 37
Illustration 4.11: First terminate the motor ground, then place motor U, V and W wires in the plug and tighten them. Illustration 4.12: Mount cable clamp to ensure 360 degree connection between chassis and shield; ensure that the outer insulation of the motor cable is removed under the clamp. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 38
Illustration 4.14: First terminate the motor ground, then place motor U, V and W wires in the terminal and tighten them. Please ensure that the outer insulation of the motor cable is removed under the EMC clamp. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
The following section describes how to terminate and access control wires. For an explanation of How to program the programming and wiring control terminals, please see the chapter entitled adjustable frequency drive MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 40
Remove front cover to access control termi- nals. When replacing the front cover, ensure proper fastening by applying a torque of 2 Illustration 4.17: A5, B1, B2, C1 and C2 enclosures MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 41
HVAC Drive Instruction Manual 4. Electrical installation 4.1.17. Control Terminals Drawing reference numbers: 10-pole plug, digital I/O. 3-pole plug, RS-485 bus. 6-pole, analog I/O. USB connection. Illustration 4.18: Control terminals (all enclosures) MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Illustration 4.20: Step 2: Insert one end in terminal 27 using a suitable terminal screwdriver. (Note: For units with the Safe Stop function, the existing jumper MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 43
This enables speed changes ► Illustration 4.23: by larger increments. Step 5: By pressing the [Hand on] button, the LED above the button should be lit and the motor may rotate. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 44
Illustration 4.27: Step 9: Change two motor wires if the desired rotation of direction is not achieved. Remove line power from the ad- justable frequency drive before changing motor wires. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 45
20, 39, and 55. This will prevent ground current interference among groups. For example, it prevents switching on digital inputs from disturbing analog inputs. NOTE Control cables must be shielded/armored. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 46
Ensure that adjustable frequency driverand motor are connected and that power is applied to adjustable frequency drive. NOTE Before power-up, ensure that connected equipment is ready for use. Step 1. Locate motor nameplate MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 47
AMA, or remove the sine wave filter during the AMA procedure. Press the [OK] key. The display should show “Press [Hand on] to start.” Press the [Hand on] key. A progress bar indicates if the AMA is in progress. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 48
"Report Value” in the [Alarm Log] shows the last measuring sequence carried out by the AMA before the adjustable frequency drive entered alarm mode. This number, along with the description of the alarm, will assist in troubleshooting. If contacting Danfoss Service, make sure to mention the number and alarm description.
The LCD display is backlit with a total of 6 alpha-numeric lines. All data is displayed on the LCP. This can show up to five operating variables while in [Status] mode. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 50
Each value/measurement readout parameter selected in par. 0-20 to par. 0-24 has its own scale and number of digits after a possible decimal point. Larger numeric values are displayed with few digits after the decimal point. Ex.: Current readout MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 51
The On LED is activated when the adjustable frequency drive receives power from AC line voltage, a DC bus terminal, or an external 24 V supply. At the same time, the back light is on. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 52
The quick menu parameters can be accessed immediately unless a password has been created via par. 0-60, 0-61, 0-65 or 0-66. It is possible to switch directly between Quick Menu mode and Main Menu mode. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 53
Menu], [Main Menu] [Alarm Log]. Use the keys to move the cur- sor. [OK] is used for choosing a parameter marked by the cursor and for allowing a pa- rameter change. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 54
[Hand on] – [Auto on]. [Reset] is used for resetting the adjustable frequency drive after an alarm (trip). It can be selected as Enable Disable Reset Keys on LCP [1] or [0] via par. 0-43 MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
The parameter values can be changed using the up/down arrows when the value is flashing. Select the main menu by pressing the [Menu] key a number of times until the main menu LED is lit. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 56
[Hand on] - [Off] - [Auto on] • Reset • Coasting stop inverse • Reversing • Set-up select lsb - Set-up select msb • Stop command from serial communication • Quick stop • DC brake MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 57
The RS-485 bus must be terminated by a resistor network at both ends. If the drive is the first on the last device in the RS-485 loop, set the switch S80 on the control card for ON. Switches S201, S202, and S801 For more information, see the paragraph MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 58
5.1.6. PC Software tools PC Software - MCT 10 All adjustable frequency drives are equipped with a serial communication port. Danfoss provides a PC tool for communication between the PC and the adjustable frequency drive, VLT Motion Control Tool MCT 10 Set-up software.
Page 59
Open the appropriate file. Choose “Write to drive.” All parameter settings are now transferred to the adjustable frequency drive. MG.10.Rx.yy A separate manual for the MCT 10 Set-up software is available: MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Ordering number: Please order the CD containing the MCT 10 Set-up software using code number 130B1000. www.danfoss.com - Business Area: MCT 10 can also be downloaded from the Danfoss website: Motion Controls 5.1.7. Tips and tricks For the majority of HVAC applications, the Quick Menu, Quick Set-up and Func- tion Set-up provide the simplest and quickest access to all the most commonly required parameters.
Page 61
Press the [OK] key. The parameter settings stored in the GLCP are now transferred to the adjustable frequency drive, as indicated by the progress bar. When 100% is reached, press [OK]. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 62
Release the keys after 5 s. The adjustable frequency drive is now programmed according to default settings. This parameter initializes everything except: 15-00 Operating Hours Power-ups 15-03 15-04 Overtemps Overvolts 15-05 MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
These parameters monitor HVAC applications. Timed actions These parameters are for actions to be performed on a daily or weekly basis, such as different references for working hours/non-working hours. Table 6.1: Parameter Groups MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 64
My Personal Menu during factory commissioning to simplify on-site commissioning/ Personal Menu fine tuning. These parameters are selected in parameter 0-25 . Up to 20 different parameters can be defined in this menu. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 65
This parameter cannot be adjusted while the motor is running. 1-20 Motor power parameter Value: 0.09 - 500 kW Size related MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 66
Speed High Limit [RPM) and par. 3-03 Maxi- mum Reference to the 87 Hz application. This parameter cannot be adjusted while the motor is running. 1-24 Motor Current Value: 0.1-10,000 A Size related MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 67
The motor speed low limit switching frequency (par. Motor must not exceed the setting in par. 4-14 14-01). Speed High Limit [Hz] Motor Speed High Limit 4-13 [RPM] Value: 0 - 60,000 RPM Size related MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 68
Illustration 6.4: Step 3: Use the up/down naviga- tion keys to scroll down to Function Set-ups. Press Illustration 6.7: Step 6: Choose parameter 6-50 Terminal 42 Output [OK]. . Press [OK]. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 69
5-13 Terminal 29 digital input 6-11 Terminal 53 high voltage 5-14 Terminal 32 digital input 6-14 Terminal 53 low ref/feedb. value 5-15 Terminal 33 digital input 6-15 Terminal 53 high ref/feedb. value MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 70
[1115] Display Text 2 [38] XIF Revision [1117] Display Text 3 [39] LON Works Revision [1118] Date and Time Readout [89] Running Hours [1501] Profibus Warning Word [953] kWh Counter [1502] MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 71
Paramdb Requests in Line [9914] Pulse Output #29 [Hz] [1670] Imbalance Derate [%] [9994] Relay Output [bin] [1671] Temperature Derate [%] [9995] Counter A [1672] Overload Derate [%] [9996] Counter B [1673] MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 72
The mean power is calculated continuously for of pulses applied to terminal 29 in digital out- the latest 120 seconds. put mode. Heatsink Temperature [°C] [1634] Present heat sink temperature of the adjust- MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 73
The options are the same as those Preventive Maintenance Word [1696] The Display Line 1.1 Small listed for par. 0-20 bits reflect the status for the programmed pre- ventive maintenance events in parameter group 23-1*. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 74
Display Text 3 in par. 0-20, Display Line XXX . Use the ▲ or ▼ but- 0-21, 0-22, 0-23 or 0-24, tons on the LCP to change a character. Use the ◀ and ▶ buttons MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 75
0-74 DST/Summertime sired speed when in Hand Mode. Value: Open-loop is also used if the adjustable fre- quency drive is part of a closed-loop control MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 76
To obtain optimal performance, reactance x , the rotor leakage reactance X the motor power factor cos-phi must be set and the main reactance X correctly. This value is set in par. 14-43, Motor MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 77
If not successful, a DC brake will be activated ning. in the time set in par. 2-02, Braking Time. Automatic Motor Adaptation See section - ap- Start will then take place from 0 Hz. plication example. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 78
Thermistor trip Stops (trips) the frequency converter when the connected ther- mistor in the motor reacts in the event of motor over-tempera- ture. The thermistor cut-out value is > 3 kΩ. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 79
Example: The frequency converter trips when the motor tem- perature is too high. Parameter set-up: Motor Thermal Protection Thermistor Trip Set Par. 1-90 Thermistor Source Analog Input 54 Set Par. 1-93 Do not select a reference source. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 80
For example ETR starts calculating when setup 3 is selected. For the North American market: The ETR functions provide class 20 motor overload protection in accordance with NEC. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 81
50 % able frequency drives with an integral dynam- Function: ic brake. Enter a value for holding current as a percent- age of the rated motor current I set in par. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 83
4-10 Motor Speed Direction Value: Clockwise 5-01 Terminal 27 Mode Both directions Value: Input Function: Selects the motor speed direction required. Output When par. 1-00 Configuration Mode is set to MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 84
Same options and functions as par. 5-1* At Torque Limit [11] ital Inputs Out of Current Range [12] Below Current, low [13] Above Current, high [14] Out of Speed Range [15] Below Speed, low [16] MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 85
[161] Local Ref. Active [165] 6-01 Live Zero Timeout Function Remote Ref. Active [166] Value: Start Cmd. Active [167] Drive in Hand Mode [168] Freeze output Drive in Auto Mode [169] MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 86
Terminal 53 Low Ref./Feedb. 6-14 Value Value: -1000000.000 to par. 6-15 0.000 Unit Function: Enter the analog input scaling value that cor- responds to the low voltage/low current set in par. 6-10 and 6-12. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 87
Enter the time constant. This is a first-order Value: digital low pass filter time constant for sup- pressing electrical noise in terminal 54. A high 0.00 – par. 6-21 0.07V time constant value improves dampening but MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 88
Power 4-20 mA [136] Scale the output to give a current lower than 20 mA at full scale, or 20 mA at an output be- Speed 4-20 mA [137] Torque 4-20 mA [138] MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 89
If a feedback is not used, its Changing the switching frequency can help to No Func- source must be set to reduce acoustic noise from the motor. tion [0]. Parameter 20-10 deter- MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 90
Feedback 2 Conversion cation protocols. Function: The adjustable frequency drive can be config- Feedback 1 Conversion par. 20-01 for de- ured to handle multi-zone applications. Two tails. different multi-zone applications are suppor- ted: MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 91
Any unused feedback results Only Setpoint 1 will be used. The sum of Set- No Function must be set to point 1 and any other references that are par. 20-00, 20-03, or 20-06. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 92
Function: any other references that are Normal [0] causes the adjustable frequency enabled (see par. group 3-1*). drive’s output frequency to decrease when the feedback is greater than the setpoint refer- MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 93
Warning: Messages in the local control panel display (if mounted) and/or signal via a relay or a digital output. Alarm: The adjustable frequency drive trips and the motor stays stopped until reset. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 94
0 - 100% bus) before entering Sleep Mode. Function: Sets the broken belt torque as a percentage of the rated motor torque. 22-41 Minimum Sleep Time Value: 0 - 600 s 10 s MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 95
Function: Sets the time desired as min. run time after a normal start command (Start/Jog/Freeze). Any normal stop command will be disregarded until the set time has expired. The timer will MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 96
For example, selecting Closed-loop ena- bles additional parameters related to closed-loop operation. Option cards added to the unit enable additional parameters associated with the option device. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
The [ ] key increases the value, the [ ] key decreases the value. ▲ ▼ Press the [Cancel] key to disregard the change, or press the [OK] key to accept the change and enter the new setting. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 98
To change the parameter value, select the indexed value and press [OK]. Change the value by using the up/down keys. Press [OK] to accept the new setting. Press [Cancel] to abort. Press [Back] to leave the parameter. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
6.2. Parameter list Parameters for VLT HVAC Drive FC 102 are grouped into various parameter groups to easily select the correct parameters for optimized operation of the adjustable frequency drive. The vast majority of HVAC applications can be programmed using the Quick Menu button and selecting the parameters under Quick Set-up and Function Set-ups.
By automatically resetting using the [Auto Reset] function, which is a default setting for par. 14-20 Reset Mode ® HVAC Drive Programming Guide, the VLT HVAC Drive; see MG.11Cx.yy NOTE After a manual reset using the [RESET] button on the LCP, the [AUTO ON] button must be pressed to restart the motor.
Page 132
Option Configuration Has Changed Safe Stop Activated Drive Initialized to Default Value Table 7.1: Alarm/Warning code list (X) Dependent on parameter LED indication Warning yellow Alarm flashing red Trip-locked yellow and red MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 133
590 ohm. WARNING/ALARM 2 Live zero error: The signal on terminal 53 or 54 is less than 50% of the value set in par. 6-10, 6-12, 6-20 or 6-22, respectively. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 134
(ETR), the motor is too hot. It can be chosen if the adjustable frequency drive is to give a warning or an alarm when the counter rea- ches 100% in par. 1-90. The fault is that the MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 135
A fitted option is not handled by the present tion disconnects and the warning is issued. control board (hardware or software). The adjustable frequency drive is still able to run, but since the brake transistor has short- MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 136
The fault could be a result of: ALARM 38 Internal fault: Ambient temperature too high Contact the local Danfoss supplier. Motor cable too long WARNING 47 ALARM 30 24 V supply low:...
Page 137
Design Guide ALARM 58 AMA internal fault: ALARM 70 Contact the local Danfoss supplier. Illegal Frequency Configuration: Current combination of control board and WARNING 59 power board is illegal. Current limit: Contact the local Danfoss supplier.
Page 138
8. Specifications ® HVAC Drive Instruction Manual MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Weight enclosure IP 21 [kg] Weight enclosure IP 55 [kg] 13.5 13.5 13.5 13.5 13.5 Weight enclosure IP 66 [kg] 13.5 13.5 13.5 13.5 13.5 Efficiency 0.96 0.96 0.96 0.96 0.96 MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 140
Estimated power loss at rated max. load [W] Weight enclosure IP 20 [kg] Weight enclosure IP 21 [kg] Weight enclosure IP 55 [kg] Weight enclosure IP 66 [kg] 0.96 0.96 0.96 0.96 Efficiency MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 141
[W] Weight enclosure IP 20 [kg] Weight enclosure IP 21 [kg] Weight enclosure IP 55 [kg] Weight enclosure IP 66 [kg] Efficiency 0.96 0.97 0.97 0.97 0.97 MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 143
Weight enclosure IP 20 [kg] Weight enclosure IP 21 [kg] Weight enclosure IP 55 [kg] Weight enclosure IP 66 [kg] Efficiency 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.99 MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 144
158°C ± 9°C [70°C ± 5°C] (Guideline - these temperatures may vary for different power sizes, enclosures, etc.). VLT HVAC drive has an auto-derating function to prevent it's heatsink from reaching 203° F [95°C].
Page 145
10 bit (+ sign) Accuracy of analog inputs Max. error 0.5% of full scale Bandwidth : 200 Hz The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 146
68 (P,TX+, RX+), 69 (N,TX-, RX-) Terminal number 61 Common for terminals 68 and 69 The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV). MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 147
Environment according to EN 60664-1 overvoltage category III/pollution degree 2 1) IEC 60947 part 4 and 5 The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV). MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 148
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-volt- age terminals. The USB connection is not galvanically isolated from protection ground. Use only an isolated laptop as a PC connection to the USB connector on the VLT HVAC Drive. MG.11.A4.22 - VLT ®...
A, using 60 PWM and a maximum for enclosure A, using SFAVM and a maximum of 32 ft. [10 m] motor cable of 32 ft. [10 m] motor cable MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 150
The cooling capability of air is decreased at a lower air pressure. At altitudes higher than 6,600 feet [2 km], please contact Danfoss Drives regarding PELV. At an altitude lower than 3,280 ft [1,000 m], no derating is necessary; but at an altitude higher than 3,280 ft [1,000 m], the ambient temperature (T ) or max.
Illustration 8.9: Derating of output current versus altitude at T . At altitudes higher than 6,600 feet [2 AMB, MAX km], please contact Danfoss Drives regarding PELV. An alternative is to lower the ambient temperature at high altitudes and thereby ensure 100% output current at high altitudes.
78, 151 Correct Mounting Of Screws Dc Hold Current/preheat Current, 2-00 Dc Hold/preheat Dc Link Default Settings Derating For Ambient Temperature Derating For Installing Long Motor Cables Or Cables With Larger Cross-section MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 153
How To Connect A Pc To The Fc 100 How To Operate The Graphical Lcp (glcp) Indexed Parameters Initialization Installation At High Altitudes (pelv) Intermediate Circuit Interval Between Starts, 22-76 Jog Speed MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 154
Motor Speed Low Limit Rpm, 4-11 Motor Thermal Protection, 1-90 Motor Voltage Motor Voltage, 1-22 Mounting Mounting A2 And A3 Mounting Of Unit Nameplate Data Nameplate Data. Nlcp No-flow Delay, 22-24 No-flow Function, 22-23 Non-ul Compliance MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 155
Start Delay Stator Leakage Reactance Status Status Messages Step-by-step Surroundings Switches S201, S202, And S801 Switching Frequency, 14-01 Terminal 27 Digital Input, 5-12 Terminal 29 Digital Input, 5-13 Terminal 29 Mode, 5-02 MG.11.A4.22 - VLT ® is a registered Danfoss trademark...
Page 156
Thermistor Source, 1-93 Three Means Of Operation Tightening Of Screws Torque Characteristics Torque Characteristics, 1-03 Type Code String Type Code String (t/c). Usb Connection. Variable Torque Voltage Level Wake-up Speed [rpm], 22-42 MG.11.A4.22 - VLT ® is a registered Danfoss trademark...