Establishing the
The power supply unit is delivered with the settings shown in bold print in
Jumper Settings
the following table.
Mark your chosen settings in the right-hand column and use this chart for the
subsequent implementation.
Function Selection
Battery monitor
–
switched on for
rechargeable battery and battery
–
switched on for battery and
off for rechargeable battery
–
switched off
Reaction of battery monitoring
following battery failure
–
/BAU signal active following
return of line voltage
–
/BAU signal active following
return of line voltage and during
operation
After failure of more than one fan or
inadequate air flow
–
PSU shutdown
–
No PSU shutdown
Voltage monitor
–
switched off
–
switched on
Relay alarm
–
driven by fan monitor and
output inhibit
–
driven only by fan monitor
System Manual
C79000-G8576-C199-06
Central Controllers and Expansion Units Power Supply Units
Jumper
Setting
MM - NN
closed
Redundant backup
MA - NA
closed
MM - NN
closed
If, for example, no redundance is
MA - NA
open
required in backup, i.e. the rechargeable
battery is missing
MM - NN
open
For example, monitoring is not needed
MA - NA
irrelevant
for EU without backup
MB - NB
open
MB - NB
closed
The possibility of evaluating the battery
monitoring during operation is
dependent on the CPU in use
F-R
closed
F-R
open
Caution: To prevent overheating of
modules, the PSU must be shut down
after 60 s at the latest (for example, by
time relay)
BA-EX
closed
Monitoring of load voltage input
switched off
BA-EX
open
Monitoring of load voltage input
switched on
Fault message initiated by fan
failure/output inhibit active; can be
f il
BB-AA
closed
signaled to control room, for example.
BB-AA
open
Fault message initiated by fan failure;
can be signaled to control room, for
example.
Application/Note
g
y
/
i hibi
i
b
(X)
4-25