Establishing the
The power supply unit is delivered with the settings shown in bold print in
Jumper Settings
the following table.
Mark your chosen settings in the right-hand column and use this chart for the
subsequent implementation.
Function Selection
Battery monitor
switched on for
rechargeable battery and battery
switched on for battery and
off for rechargeable battery
switched off
Reaction of battery monitoring
following battery failure
/BAU signal active following
return of line voltage
/BAU signal active following
return of line voltage and during
operation
After failure of more than one fan or
inadequate air flow
PSU shutdown
No PSU shutdown
Voltage monitor
switched off
switched on
Relay alarm
driven by fan monitor and
output inhibit
driven only by fan monitor
System Manual
C79000-G8576-C199-06
Central Controllers and Expansion Units Power Supply Units
Jumper
Setting
MM - NN
closed
Redundant backup
MA - NA
closed
MM - NN
closed
If, for example, no redundance is
MA - NA
open
required in backup, i.e. the rechargeable
battery is missing
MM - NN
open
For example, monitoring is not needed
MA - NA
irrelevant
for EU without backup
MB - NB
open
MB - NB
closed
The possibility of evaluating the battery
monitoring during operation is
dependent on the CPU in use
F-R
closed
F-R
open
Caution: To prevent overheating of
modules, the PSU must be shut down
after 60 s at the latest (for example, by
time relay)
BA-EX
closed
Monitoring of load voltage input
switched off
BA-EX
open
Monitoring of load voltage input
switched on
Fault message initiated by fan
failure/output inhibit active; can be
f il
BB-AA
closed
signaled to control room, for example.
BB-AA
open
Fault message initiated by fan failure;
can be signaled to control room, for
example.
Application/Note
g
y
/
i hibi
i
b
(X)
4-25