Siemens S5-135U/155U System Manual page 322

Siemens network card system manual
Table of Contents

Advertisement

Digital Input/Output Modules
0
1
2
3
4
5
6
: OFF
7
: ON
Process Interrupt via IR-C
Figure 8-4
Switch Settings for Operation with Process Alarm via Interrupt (Example)
Operation with
In this mode, a process alarm is initiated via input byte IB 0. This mode is
Process Alarm
only possible in conjunction with a CPU 948 in single-processor operation.
via IB 0
To operate the 432 digital input module with process alarm via IB 0, you can
insert it at any I/O slot.
When you use the module in the CC, you must not set any other input
module to address 0 (i.e. neither in the normal (P) nor in the extended (O)
area).
If you use the module in an EU which is addressed in the normal area, you
must not set any other input module in the EU to address 0 in the normal
area.
So that the module can initiate a process alarm for a change of logic state, the
alarm must be processed by an alarm routine (alarm OB) in the user program,
with automatic acknowledgement of the alarm. To avoid loss of an alarm, it
must not be possible for the alarm OB to be interrupted by process alarms.
The CPU must process the process alarms with level triggering (see
Programming Guide of the CPU).
Scanning the
Example:
Process Inputs
Program the following in the alarm OB which you have preset with byte IB 0
and switch S2:
8-10
S1
S2
IR-A
0
Bit 0
IR-B
1
Bit 1
2
IR-C
Bit 2
IR-D
3
Bit 3
IR-E
4
Bit 4
IR-F
5
Bit 5
IR-G
6
Bit 6
INT
7
Bit 7
L
PW128
(load I/O word)
T
FW0
(transfer flag word)
L
PW130
etc.
T
FW2
S3
0
}
Byte 3
1
2
}
Byte 2
3
4
}
Byte 1
5
6
}
Byte 0
7
Byte 0: Positive-Going Edge
Byte 1: Negative-Going Edge-
Byte 2: Both Edges
Byte 3: No Process Interrupt
System Manual
C79000-G8576-C199-06