Technical Specifications - Siemens S5-135U/155U System Manual

Siemens network card system manual
Table of Contents

Advertisement

9.4.9

Technical Specifications

6ES5 463-4UA12 and 6ES5 463-4UB12 Analog Input Modules
Rated input ranges
(selectable at front connector)
Number of inputs
Measured value representation
Overrange
Error signal for overflow
Measuring principle
Conversion principle
Isolation
Permissible potential difference between ref. potentials of
sensors and module (U
) and between sensors (chan-
CM
nels)
Power Supply
– digital section from system bus
– analog section from load voltage
– enabling of module F+/F-
Integration time
– 463-4UA12
– 463-4UB12
Encoding time per measured value
– 463-4UA12
– 463-4UB12
Cycle time for 4 measured values (max. delay time of
measured value acquisition)
– 463-4UA12
– 463-4UB12
Input resistance for input ranges
1 V
10 V
20 mA
4 to 20 mA
Max. permissible input voltage without destruction
Interference suppression
– with common-mode interference
– with differential-mode interference
Error, referred to
– rated value
– linearity
– tolerance
– temperature error
Voltage test to VDE 0160
Surge voltage test to IEC 255-4
System Manual
C79000-G8576-C199-06
Analog Input/Output Modules
- 0.05 to + 1 V
- 0.5 to + 10 V
-1 to + 20 mA
+ 4 to 20 mA for 2-wire transducer
+ 4 to 20 mA for 4-wire transducer
4 voltage/current inputs
11 bits (two's complement)
1024 units in rated range
50 % (with full accuracy)
Yes (upward of 50 % overrange)
Integrating
Voltage-frequency conversion
Yes, 4 inputs with respect to 0 V and each other
25 V AC/60 V DC max.
5 V
5 %; 150 mA typical
24 V; approx. 150 mA
24 V; approx. 7 mA
20 ms at 50 Hz
2
16
/
ms at 60 Hz
3
20 ms at 50 Hz
2
16
/
ms at 60 Hz
3
20 ms at 50 Hz
2
16
/
ms at 60 Hz
3
> 10 M
90 k
50
62.5
30 V; 75V for 1 ms max. and duty ratio 1:10
> 80 dB (f = 0 to 50 kHz)
> 40 dB (V
0.1 U
)
noise
N
–4
5 x 10
1 unit
3 units
–4
0.6 x 10
/K
Between inputs and ground point, and between 2 inputs;
tested at 500 V AC
Between inputs and L-: Vp = 1kV; 1.2/50 s
9-47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uS5-155u