Installation And Startup - Siemens S5-135U/155U System Manual

Siemens network card system manual
Table of Contents

Advertisement

CPUs, Memory Cards, Memory Submodules, Interface Submodules
5.5.2

Installation and Startup

Removing and
Inserting the
Module
Caution
!
Switch off the power supply before removing or inserting the module.
Insertion
Proceed as follows to insert the CPU in the central controller:
Step
Note
If you install the CPU 928 -3UA21 as the replacement for a double-width
CPU, you must cover the slot which has been freed up with a blanking plate.
Removal
Proceed as follows to remove the CPU:
Step
5-56
Action
1
Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.
2
Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U from slot 11.
3
Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.
4
Press the locking pin inwards on the bottom of the module and
o
rotate it 90
clockwise.
5
Secure the upper locking bar.
Action
1
Release the upper locking bar of the central controller.
2
Release the locking pin of the module.
3
Press the release lever downwards and pull the module forwards
and out of the central controller.
System Manual
C79000-G8576-C199-06

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uS5-155u

Table of Contents