Technical Specifications - Siemens S5-135U/155U System Manual

Siemens network card system manual
Table of Contents

Advertisement

9.3.15

Technical Specifications

6ES5 460-4UA13 Analog Input Module
Rated input ranges with cards for every 4 channels
– 6ES5 498-1AA11
– 6ES5 498-1AA21
– 6ES5 498-1AA31
– 6ES5 498-1AA41
– 6ES5 498-1AA51
– 6ES5 498-1AA61
– 6ES5 498-1AA71
Number of inputs
Measured-value representation
Measuring principle
Isolation
Permissible potential difference between reference potentials
of sensors and the module (U
CM
nels)
Power Supply
– digital section from system bus
– analog section from load voltage
– enabling for module F+/F-
– tripping current L+
Constant current source for Pt 100 connection I
Integration time
Encoding time per measured value
1)
System Manual
C79000-G8576-C199-06
4 to 20 mA for two-wire transducer
4 to 20 mA for four-wire transducer
8 voltage/current inputs or
8 resistance inputs (Pt 100)
13 bits (two's complement) or 12 bits + sign;
512 to 2560 units for 4 to 20 mA
Integrating
Yes
8 inputs tested with respect to 0 V at 500 V AC
25 V AC/60 V DC max.
) and between sensors (chan-
5 V
24 V; approx. 50 mA
24 V; approx. 5 mA
24 V; approx. 5 mA
/I
2.5 mA; TC =
C+
C-
20 ms at 50 Hz; 16
60 ms at 50 Hz; 50 ms at 60 Hz
Plus 20 mA max. per connected two-wire transducer.
Analog Input/Output Modules
12.5 mV/ 50 mV/ 500 mV/Pt 100
1 V
10 V
5 mA/
20 mA
5 V
2048 units in rated range;
5 %; 130 mA typical
1)
–5
5 x 10
/K
2
/
ms at 60 Hz
3
9-29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uS5-155u