Monitoring Module
10.3.1
Addressing
Example 1
S5-130K, S5-135U or S5-155U
1st MM
S1 e.g.
S2 e.g.
S3
S4
User program in OB 1 or FB 0
without S5-DOS
L
T
L
T
L
T
BE
3)
Possible addresses 0 (00H) to 255 (FFH)
4)
To achieve optimum fault detection, set the inverse addresses 85 (55H) and 170 (AAH) at S1 and S2.
5)
Since the addresses of the monitoring module switches S3 and S4 are not acknowledged, this must be done by the
monitoring module contained in the last expansion unit (the most remote from the central controller). The addresses
85 (55H) or 170 (AAH) of this monitoring module must be coded at switches S1 or S2, respectively.
These addresses may no longer be occupied for I/O tasks.
10-10
2nd MM
3)
127 (7FH)
e.g.
3)
127 (7FH)
e.g.
5)
85 (55H)
5)
170 (AAH)
with S5-DOS
EB
127
L
AB
127
T
EB
126
L
AB
126
T
EB
85
L
PB
170
T
BE
3rd MM in the
last EU
3)
126
(7EH)
85
3)
126
(7EH)
170
5)
85
(55H)
85
5)
170
(AAH)
170
PY
127
PY
127
PY
126
PY
126
PY
85
PY
170
C79000-G8576-C199-06
4)
(55H)
4)
(AAH)
5)
(55H)
5)
(AAH)
System Manual