Siemens S5-135U/155U System Manual page 372

Siemens network card system manual
Table of Contents

Advertisement

Digital Input/Output Modules
8.4.15
6ES5 456-4UB12 Digital Output Module
Rated supply voltage L
Number of outputs
Isolation
Range for supply voltage
Fusing
Output voltage
for logic 1
for logic 0
Residual current at logic 0
Switching current (resistive, inductive load)
ventilated
not ventilated
Switching current for lamps
ventilated
not ventilated
Contactor size
Max. inrush current for
3 ms
20 ms
50 ms
Switching capacity per module
for UL
for CSA
Permissible line length
Power supply
Digital section from system bus
Power dissipation (rated operation)
Enable input (F+/F–)
Voltage test to VDE 0160
Mechanical specifications
Dimensions (W x H x D)
Weight
1)
Protected by a fuse.
2)
Contactors of Series 3TJ can only be operated at 115 V AC.
8-60
115 to 230 V AC (47 to 63 Hz)
8, conditional short-circuit protection
Yes, 8 outputs
88 to 264 V AC
3.5 A fast; 1 fuse per output
L– 1.5 V min.
30 V max.
5 mA max.
2)
40 mA to 2 A;
2)
40 mA to 1 A;
40 mA to 2 A;
40 mA to 1 A;
0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC;
00 (Type 3TJ ..) to 8 (Type 3TB52) at 115 V AC;
16 A
8 A
6.5 A
1440 VA max.
2000 VA max.
300 m max. unshielded
5 V, 100 mA typical
18.0 W
Jumper in front connector
Between two groups: 2000 V AC
Between group and ground point: 1500 V AC
40 mm x 255 mm x 195 mm
Approx. 0.6 kg
1)
System Manual
C79000-G8576-C199-06

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uS5-155u

Table of Contents