Setting The Address Switches S1, S2, S3, S4 - Siemens S5-135U/155U System Manual

Siemens network card system manual
Table of Contents

Advertisement

Monitoring Module
10.3.2

Setting the Address Switches S1, S2, S3, S4

The addresses are set as one-byte addresses as in the case of I/O modules.
The significance of the rockers pressed down to ON at the switches must be
added.
Example
Address 85 is to be set.
rockers to be pressed down to ON
10-12
8
7
6
5
4
3
2
1 (ADB 0)
3 (ADB 2)
5 (ADB 4)
7 (ADB 6)
7
6
5
4
3
2
1
8
1
OFF
ON
ADB 0 Significance 1
ADB 1 Significance
ADB 2 Significance
ADB 3 Significance
ADB 4 Significance 16
ADB 5 Significance 32
ADB 6 Significance 64
ADB 7 Significance 128
Significance
OFF
ON
C79000-G8576-C199-06
2
4
8
1
4
16
64
85
System Manual