Fan Submodules; Technical Description - Siemens S5-135U/155U System Manual

Siemens network card system manual
Table of Contents

Advertisement

Central Controllers and Expansion Units Power Supply Units
4.5

Fan Submodules

4.5.1

Technical Description

The fan submodule variants 6ES5 988-3LA11 (230 V AC) and
6ES5 988-3NA11 (24 V DC) are described in the following section.
A fan submodule has the following function:
Connections and
The following terminals and LEDs are fitted on the front plate (the front
LEDs
plate of the -3LA11 is shown as an example):
SIEMENS
AC line
AC 230V
CAUTION!
Disconnect
before
removing
power supply!
Voltage selector
inside the unit!
L1 N
ID
Label
Element
1
2
3
230V AC
Screw
terminals
L1, N
24V DC
Screw
terminals + –
4
Monitor Output Relay output
5
Fan Fault
Red LED
4-70
Heat dissipation
The fan submodule dissipates any excess heat created in the central
controller or expansion unit.
Monitor Output
Relay max.
250V AC/3A
Fan
Fault
1
2
3
Use copper wire 60/75 C only!
Tightening torque: terminals 0,8Nm/ 1,8 Nm
Protective conductor terminal for fan submodule and housing.
ZStrain reliefs for connecting cables, with metal contact surface for cable
shields.
AC connection
(details for -3LA11)
24 V DC supply
(details for -3NA11)
Standstill of one or both fans is signaled via LED and relay contact.