FLEX I/O DeviceNet Adapter Module
– The original configuration of the adapter is the same as the v3.001
out-of-the-box configuration of the adapter.
In this case, the scanner will automatically make the I/O connection
with the firmware revision 3.001 adapter. Once network setup is
complete, downloading, and saving the original configuration to the
adapter is recommended.
– The original configuration of the adapter does not match the
firmware revision 3.001 out-of-the-box configuration of the adapter.
In this case, the scanner will report an error 77, indicating an I/O
size mismatch.
To correct this issue, download the existing configuration to
the adapter.
ATTENTION: The adapter will not accept any downloads that could change its
configuration while there is an active I/O connection between a scanner and the
adapter. It will be necessary to either remove the scanner from the network or
disable the scanlist entry in the scanner to the adapter, using RSNetWorx™
software, before configuration downloads can be done successfully to
the adapter.

Specifications

General
Attribute
I/O capacity
Power supply
Supply voltage
Input voltage rating
16
Rockwell Automation Publication 1794-IN099D-EN-P - November 2018
Value
8 modules
The 24V DC power supply must be capable of providing a turn-on
inrush surge current of 14 A for 5 ms for each adapter connected to this
supply.
Power supply: 19.2...31.2V DC, 400 mA
DeviceNet power: 24V DC, 90 mA, Class 2
Flexbus output: 5V DC, 640 mA
24V DC nom
19.2V to 31.2V DC (includes 5% AC ripple)