European Hazardous Location Approval

The following applies to products marked
• Are intended for use in potentially explosive atmospheres as defined by European Union
Directive 2014/34/EU and has been found to comply with the Essential Health and Safety
Requirements relating to the design and construction of Category 3 equipment intended for
use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
• Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.
• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and
Safety Requirements relating to the design and construction of such equipment given in
Annex II to Directive 2014/34/EU. See the EC Declaration of Conformity at
http://www.rockwellautomation.com/global/certification/overview.page
• The type of protection is Ex nA IIC T4 Gc according to EN 60079-15.
• Comply to Standards EN 60079-0:2012, EN 60079-15:2010, reference certificate number
LCIE 01 ATEX 6020 X I 09; II3G Ex nA IIC T4 Gc.
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists,
or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such
locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.
• May have catalog numbers followed by a "K" to indicate a conformal coating option.

Electrical Safety Considerations

ATTENTION: Power to this equipment and all connected I/O must be supplied
from a source compliant with the following:
• SELV source approved to EN/IEC60950-1, EN/IEC61010-2-201
or EN/IEC62368-1 (ES1)
• PELV source approved to EN/IEC60950-1, EN/IEC61010-2-201
or EN/IEC62368-1 (ES1)
Note: A power source approved to a U.S.A. or Canadian version of the above listed
standards is required for system approval in the U.S.A. or Canada.
ATTENTION: All wiring must comply with applicable electrical installation
requirements (e.g., N.E.C. article 501-4(b)).
ATTENTION: Wire conductor and insulation ratings shall support minimum
temperature rating of 85 °C (185 °F)
Rockwell Automation Publication 1794-IN099D-EN-P - November 2018
FLEX I/O DeviceNet Adapter Module
for details.