5-2
Monitoring and Troubleshooting Your ControlNet System
Indicator
PROC
FORCE
COMM
1785-UM022B-EN-P - February 2002
Color
Description
Green
Processor is in run
(steady)
mode and fully
operational
Green
Processor memory is
(blinking)
being transferred to
EEPROM
Red
Major fault
(blinking)
Alternating
Processor in
Red and
FLASH-memory
Green
programming mode
Red
Power cycle with
problem battery
(steady)
Red
Fault with memory
loss
(steady)
Off
Processor is in
program load or test
mode or is not
receiving power
Amber
SFC and/or I/O forces
(steady)
enabled
Amber
SFC and/or I/O forces
(blinking)
present but not
enabled
Off
SFC and/or I/O forces
not present
Off
No transmission on
channel 0
Green
Transmission on
(blinking)
channel 0
Probable Cause
Recommended Action
Normal operation
No action required
Normal operation
No action required
• RSLogix 5
During RSLogix 5 download, this is
download in
normal operation - wait for
progress
download to complete.
• Run-time error
If not during RSLogix 5 download:
• Check major fault bit in status
file (S:11) for error definition
• Clear fault, correct problem, and
return to run mode
Normal operation if
No action required - allow flash
processor's FLASH
update to complete
memory is being
reprogrammed
Battery is low,
Properly replace or install battery
disconnected or not
(see Chapter 1 for more
installed
information)
• New processor
• Use programming software to
clear and initialize memory
• Invalid ControlNet
• Verify that ControlNet address
network address
switch is not set to 0
• Processor has
• Install battery (to preserve
failed internal
failure diagnostics), then power
diagnostics
down, reseat processor and
power up; then reload your
program. If you are unable to
reload your program, replace the
processor. If you are able to
reload your program and fault
persists, contact Technical
Support at 440.646.6800 to
diagnose the problem.
Check power supply and
connections
Normal operation
No action required
Normal operation if
channel is not being
used
Normal operation if
channel is being
used