Allen-Bradley ControlNet PLC-5 User Manual page 125

Hide thumbs Also See for ControlNet PLC-5:
Table of Contents

Advertisement

Decimal
Hex. Code
Error Message
Code
38
0x0026
INVALID DESTINATION
ADDRESS SIZE
256
0x0100
CONNECTION IN USE
262
0x0106
CONNECTION USED BY OTHER
NODE
263
0x0107
CONNECTION NOT FOUND
265
0x0109
INVALID CONNECTION SIZE
273
0x0111
INVALID RPI
275
0x0113
OUT OF CONNECTIONS
276
0x0114
PRODUCT CODE MISMATCH
277
0x0115
PRODUCT TYPE MISMATCH
278
0x0116
REVISION MISMATCH
ControlNet I/O Map-Entry Status Words and Error Codes
Explanation/Possible Cause(s)
The map table is corrupted.
The target node of the MSG
instruction is not a processor or the
target node of the CIO instruction is
not the correct I/O adapter.
The connection at the target node is
already in use.
The originating node attempted to
use a connection that is already
being used by another node.
A non-discrete connection is setup
to a discrete module.
The connection at the target node
does not exist.
The originating node requested a
connection size that the target node
cannot accommodate.
The target node cannot produce the
data at or faster than the requested
packet interval (RPI) entered in the
map table.
The maximum number of
connections to/from this node has
been exceeded.
The target node/module does not
match the node/module entered in
the map table.
The series/revision of the target
node/module does not match the
series/revision entered in the map
table.
AB Drives
Possible Corrective Action(s)
Reenter the I/O map entry that is
failing.
Edit the ladder program so that the
correct target node is used.
Replace the target node with the
correct type of node.
No action is required. The
connection can be re-established
after the target node times out the
old connection.
Delete or inhibit any other node's
connection so that the preferred
node can establish the connection.
Replace the target module with the
correct non-discrete module.
Correct the I/O map table.
Make sure I/O map entries exist in
the I/O map tables of both the
originating and target nodes.
Correct the connection size in the
map table. If it is a listen-only
connection, make sure that the
connection size is not larger that the
size of the controlling connection.
Set the addressing mode switches
of the 1771 rack dip correctly.
Use a rack with the correct number
of slots.
Increase the requested packet
interval (RPI) entered in the map
table.
Reduce the number of I/O
connections, MSG instructions, or
CIO instructions to/from this node.
Replace the target node/module
with the correct node/module.
Correct the I/O map table.
Replace the target node/module
with the correct node/module.
Correct the I/O map table.
1785-UM022B-EN-P - February 2002
D-5