Decimal
Hex. Code
Error Message
Code
65523
0xFFF3
CONTROLNET TRANSFER
QUEUE FULL
65527
0xFFF7
MODULE TIMED OUT
65529
0xFFF9
COMMUNICATION ERROR
CAUSED LOSS OF DATA
ControlNet I/O Map-Entry Status Words and Error Codes
Explanation/Possible Cause(s)
The immediate CIO instruction could
not be executed because the queue
is full.
The target slot is empty.
The target slot contains the wrong
module type.
An incorrect module or slot was
entered in the map table.
A communication error between the
adapter and the module caused the
transfer to be aborted.
The target slot contains the wrong
module type.
An incorrect module or slot was
entered in the I/O map table.
AB Drives
Possible Corrective Action(s)
Edit the ladder program so that the
number of active 1771 READ/WRITE
CIO instructions is equal to or less
than the maximum of 32.
Insert the proper module in the
correct slot of the target node.
Edit the I/O map table to show the
correct module type and slot.
Make sure that the module is
properly seated in the correct slot of
the target node.
Make sure that the adapter's power
supply is providing the proper
voltage.
Insert the proper module in the
correct slot of the target node.
Edit the I/O map table to show the
correct module type and slot.
1785-UM022B-EN-P - February 2002