D-8
ControlNet I/O Map-Entry Status Words and Error Codes
Decimal
Hex. Code
Code
774
0x0306
789
0x0315
791
0x0317
797
0x31D
798
0x31E
65522
0xFFF2
1785-UM022B-EN-P - February 2002
Error Message
KEEPER NOT AVAILABLE
INVALID PATH SEGMENT TYPE
INVALID SCHEDULE DATA
INVALID TARGET TAG
REDUNDANT CONNECTION
MISMATCH
TAG IS ALREADY PRODUCED
THE MAXIMUM NUMBER OF
TIMES
CONFIGURATION FROM MAP
ENTRY FAILED
Explanation/Possible Cause(s)
The ControlNet cable from the
originating node to the keeper is
broken or disconnected.
The keeper is not powered.
No keeper exists on the ControlNet
network.
The map table is corrupted.
The target node of the CIO
instruction is not the correct I/O
adapter.
The ControlNet cable from the
originating node to the programming
terminal was broken or
disconnected when the ControlNet
network was configured.
The originating node was not
powered when the ControlNet
network was configured.
The PLC-5C is requesting data from
a ControlLogix tag that is not
configured as a producer.
Configuration for this redundant
connection does not match the
configuration used by the Hot
Backup partner.
The PLC-5C is requesting data from
a ControlLogix tag that is already
being producted the maximum
number of times.
The ControlNet cable from the
originating node to the target node is
broken or disconnected.
The target node is not powered.
The target slot is empty.
The target slot contains the wrong
module type.
An incorrect module or slot was
entered in the map table.
Possible Corrective Action(s)
Fix and/or reconnect the ControlNet
cable.
Supply power to at least one
ControlNet processor.
Add at least one ContolNet
processor to the network.
Reconfigure the ControlNet network
by enabling and accepting edits with
RSNetWorx.
Reenter the I/O map entry that is
failing.
Edit the ladder program so that the
correct target node is used.
Replace the target node with the
correct adapter.
Fix and/or reconnect the ControlNet
cable and reconfigure the ControlNet
network.
Supply power to the originating node
and reconfigure the ControlNet
network.
Change the PLC-5C I/O map entry to
use the correct tag.
Reconfigure the tag in the
ControlLogix processor to be a
producer.
Change the PLC-5C I/O map and
module configuration data to match
the Hot Backup partner.
In the ControlLogix processor,
increase the number of times this
tag can produce data.
Fix and/or reconnect the ControlNet
cable.
Supply power to the target node.
Insert the proper module in the
correct slot of the target node.
Edit the I/O map table to show the
correct module type and slot.