Allen-Bradley ControlNet PLC-5 User Manual page 21

Hide thumbs Also See for ControlNet PLC-5:
Table of Contents

Advertisement

5
To install or replace the battery:
1. Remove the battery from the shipping bag.
2. Remove the battery cover from the processor.
3. If you are replacing an existing battery, detach the wired clip from
the mating connector on the processor and remove the battery.
4. Connect the new or replacement battery by attaching the wired
clip to the mating connector on the processor.
5. Place the battery and tuck the wires inside the battery area on the
processor.
6. Replace the battery cover.
7. Use a pencil or erasable pen to write the battery installation date
on the battery cover.
WARNING
!
AB Drives
Installing Your ControlNet PLC-5 Processor
When you connect or disconnect the battery, an
electrical arc can occur. This could cause an
explosion in hazardous location installations. Be
sure that power is removed or the area is
nonhazardous before proceeding.
• For safety information on the handling of lithium
batteries, including handling and disposal of
leaking batteries, refer to Guidelines for
Handling Lithium Batteries, publication AG-5.4
• Store batteries in a cool, dry environment. We
recommend 25° C with 40% or 60% relative
humidity. You may store batteries up to 30 days
between -45° - 85° C, such as during
transportation. To avoid possible leakage, do not
store batteries above 60° C for more than 30
days.
1785-UM022B-EN-P - February 2002