ControlNet Diagnostics File Layout
When you specify a Control Diagnostic File in RSNetWorx for the
ControlNet network, the PLC-520C, -5/40C, -5/46C or -5/80C
processor copies the 40 words of diagnostic counters into the
specified integer file.
Twenty-three additional diagnostic counters are available in the
ControlNet diagnostic file. To access these counters, you must first
use RSLogix5 to increase the size of the ControlNet diagnostic
integer file to 63 words.
The layout of the ControlNet diagnostic file is described in the
following table. The processor updates this file once every second.
Field Names
Buffer Errors
Last 8 Nodes from which bad packets were received
Good Frames Transmitted (center significant byte)
Good Frames Transmitted (least significant byte)
Good Frames Received (least significant byte)
Good Frames Transmitted (most significant byte)
Good Frames Received (most significant byte)
Good Frames Received (center significant byte)
Channel A Errors
Bad Received Frames
Aborted Frames Transmitted
Channel B Errors
NUI Overloads
Highwaters/Out-of-Steps
Blockages
Slot Overloads
Aborted Frames Received
Non-Concurrences
Frames with Duplicate Node Address Received
Lonely Occurrences
Collisions
Noise Hits
AB Drives
Moderators from non-lowmen
Appendix
1
File Offset
(word;bits)
0;15-00
1-4;
5;07-00
5;15-08
6;07-00
6;15-08
7;07-00
7;15-08
8;07-00
8;15-08
9;07-00
9;15-08
10;07-00
10;15-08
11;07-00
11;15-08
12;07-00
12;15-08
13;07-00
13;15-08
14;07-00
14;15-08
15;07-00