B-8
Processor Status File
This
fault
code:
Indicates this fault:
201
ControlNet input data missed.
The processor is unable to process incoming data from the network.
202
ControlNet diagnostic data missed.
203
ControlNet schedule transmit data overflow.
204
Too many output connections per NUI.
1785-UM022B-EN-P - February 2002
And the fault is:
Recoverable
Check your network for
missing terminators or other
sources of electrical noise
(see the Industrial
Automation Wiring and
Grounding Guidelines,
publication 1770-4.1).
Recoverable
Contact your local Rockwell
Automation representative if
you get this message.
Recoverable
Contact your local Rockwell
Automation representative if
you get this message.
Recoverable
Make scheduled outputs
with short Requested Packet
Intervals longer and reaccept
edits for the ControlNet
configuration.