B-6
Processor Status File
This
fault
code:
Indicates this fault:
41
NXT instruction with missing FOR
42
You tried to jump to a non-existent label
43
File is not an SFC
44
Error using SFR. This error occurs if:
• you tried to reset into a simultaneous path
• you specified a step reference number that is not found or is not tied to a step (it is a transition)
• the previous SFR to a different step is not complete
45
Invalid channel number entered
46
Length operand of IDI or IDO instruction is greater than the maximum allowed
47
SFC action overlap. An action was still active when the step became re-activated
48-69
Reserved
70
The processor detected duplicate labels
71
The processor tried to start an SFC subchart that is already running
72
The processor tried to stop an SFC subchart that isn't running
73
The processor tried to start more than the allowed number of subcharts
74
SFC file error detected
75
The SFC has too many active functions
76
SFC step loops back to itself.
77
The SFC references a step, transition, subchart, or SC file that is missing, empty or too small
78
The processor cannot continue to run the SFC after power loss
79
You tried to download an SFC to a processor that cannot run SFCs
80
You have an I/O configuration error
81
You illegally set an I/O chassis backplane switch by setting both switch 4 and 5 on
82
Illegal cartridge type for selected operation. This error also occurs if the processor doesn't have a
memory module, but the backplane switches are set for a memory module. Make sure the backplane
switches are correct (set switch 6 ON and switch 7 OFF if the processor doesn't have a memory module).
1785-UM022B-EN-P - February 2002
And the fault is:
Non-recoverable
the fault routine will be
executed but cannot clear
major fault bit 2.
Recoverable
Non-recoverable
Recoverable
Recoverable