Decimal
Hex. Code
Error Message
Code
516
0x0204
UNCONNECTED REQUEST
TIMED OUT
769
0x0301
OUT OF BUFFER MEMORY
770
0x0302
SCHEDULED BANDWIDTH NOT
AVAILABLE
772
0x0304
NO SCHEDULED
CONFIGURATION
773
0x0305
SCANNER SIGNATURE
MISMATCH
ControlNet I/O Map-Entry Status Words and Error Codes
Explanation/Possible Cause(s)
The ControlNet cable from the
originating node to the target node is
broken or disconnected.
The target node is not powered.
The originator's and/or the target's
node number is greater than UMAX.
The target node is too busy to
respond.
The maximum number of
connections to/from this node has
been exceeded.
There are too many words
scheduled for transmission.
The network update time (NUT) is
too small.
The originator's and/or the target's
node number is greater than SMAX.
The ControlNet cable from the
originating node to the keeper was
broken or disconnected when the
ControlNet network was configured.
The keeper was not powered when
the ControlNet network was
configured.
The originating and/or target node is
not properly configured to send
scheduled data.
The ControlNet cable from the
originating node to the keeper was
broken or disconnected when the
ControlNet network was configured.
The ControlNet processor was not
configured on the current network.
The ControlNet network was formed
by joining two existing ControlNet
networks.
AB Drives
Possible Corrective Action(s)
Fix and/or reconnect the ControlNet
cable.
Supply power to the target node.
Reconfigure the ControlNet network
so that the originator's and target's
node numbers are less than or equal
to UMAX.
Reduce the number of unconnected
requests to the target node.
• If this is an I/O connection, reduce
the number of I/O connections.
• If this is a MSG instruction,
reduce the number of MSG
instructions.
• If this is a CIO instruction, reduce
the number of CIO instructions.
Edit the I/O map table to reduce the
number of scheduled words.
Increase the network update time
(NUT).
Reconfigure the ControlNet network
so that the originator's and target's
node numbers are less than or equal
to SMAX.
Fix and/or reconnect the ControlNet
cable and reconfigure the ControlNet
network.
Supply power to the keeper and
reconfigure the ControlNet network.
Edit the I/O map table of the
originating and/or target nodes to
send scheduled data.
Fix and/or reconnect the ControlNet
cable. Reconfigure the ControlNet
network by enabling and accepting
edits with RSNetWorx.
Reconfigure the ControlNet network
by enabling and accepting edits with
RSNetWorx.
Reconfigure the new ControlNet
network by enabling and accepting
edits with RSNetWorx.
1785-UM022B-EN-P - February 2002
D-7