Safety, approvals, EMC

7.2 Test voltage

7.2
Test voltage
Figure 7-1
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another
● Connect the output terminals, signaling contact, remote and PE with one another
Test (C)
● Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1
Test voltage for 6EP3436-8SB00-0AY0, 6EP3446-8SB10-0AY0, 6EP3446-8SB00-0AY0, 6EP3424-8UB00-
0AY0 and 6EP3436-8UB00-0AY0
Type test
Production test
Field test
Note:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
86
Test voltage diagram
Test time
Prim ↔ sec (A)
60 s
4200 V DC
60 s
3000 V AC
1 s
4200 V DC
1 s
3000 V AC
1 s
2200 V DC
1 s
1500 V AC
Prim ↔ PE (B)
Sec ↔ PE (C)
2200 V DC
700 V DC
1500 V AC
500 V AC
4200 V DC
500 V DC
3000 V AC
350 V AC
2200 V DC
500 V DC
1500 V AC
350 V AC