Protection And Monitoring - Siemens SITOP PSU8200 24 V/20 A User Manual

3ph
Hide thumbs Also See for SITOP PSU8200 24 V/20 A:
Table of Contents

Advertisement

Technical data

6.5 Protection and monitoring

6.5
Protection and monitoring
Output overvoltage protec-
tion
Current limitation, typ.
Property of the output: short-
circuit proof
Short-circuit protection
Continuous short-circuit
current: rms value, typ.
Remark
Overload / short-circuit indi-
cator
Output overvoltage protec-
tion
Current limitation, typ.
Property of the output: short-
circuit proof
Short-circuit protection
Continuous short-circuit
current: Rms value, typ.
Remark
Overload / short-circuit indi-
cator
Output overvoltage protec-
tion
Current limit, typ.
Property of the output: short-
circuit proof
78
6EP3436-8SB00-0AY0
(24 V/20 A)
< 35 V (PR1)
< 31.8 V (from PR2)
23 A
Yes
Optional constant current
characteristic approx. 23 A
or latching shutdown
23 A
Overload capability 150 %
I
up to 5 s/min
out rated
Yellow LED for "overload",
red LED for "latching shut-
down"
6EP3446-8SB10-0AY0
(36 V/13 A)
< 48 V
14 A
Yes
Optional constant current
characteristic approx. 14 A
or latching shutdown
14 A
Overload capability 150 %
I
up to 5 s/min
out rated
Yellow LED for "overload",
red LED for "latching shut-
down"
6EP3424-8UB00-0AY0
(12 V/20 A)
< 18 V
22 A
Yes
6EP1437-3BA10
(24 V/40 A)
< 31.8 V
44 A
Yes
Optional constant current
characteristic approx. 44 A
or latching shutdown
44 A
Overload capability 150 %
I
up to 5 s/min
out rated
Yellow LED for "overload",
red LED for "latching shut-
down"
6EP3446-8SB00-0AY0
(48 V/10 A)
< 60 V
11 A
Yes
Optional constant current
characteristic approx. 11 A
or latching shutdown
11 A
Overload capability 150 %
I
up to 5 s/min
out rated
Yellow LED for "overload",
red LED for "latching shut-
down"
6EP3436-8UB00-0AY0
(24 V/17 A)
< 31.8 V
19 A
Yes
Manual, 05.2018, C98130-A7638-A1-6-7629
6EP3437-8SB00-0AY0
(24 V/40 A)
< 31.8 V
50 A
Yes
Optional constant current
characteristic approx. 50 A
or latching shutdown
50 A
Overload capability 150 %
I
up to 5 s/min
out rated
Yellow LED for "overload",
red LED for "latching shut-
down"
6EP3447-8SB00-0AY0
< 60 V
25 A
Yes
Optional constant current
characteristic approx. 25 A
or latching shutdown
25 A
Overload capability 150 %
I
up to 5 s/min
out rated
Yellow LED for "overload",
red LED for "latching shut-
down"
6EP3437-8UB00-0AY0
(24 V/40 A)
< 31.8 V
50 A
Yes
SITOP PSU8200/3800 3ph

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop psu8200 36 v/13 aSitop psu8200 48 v/10 aSitop psu8200 48 v/20 aSitop psu3800 24 v/17 aSitop psu3800 12 v/20 aSitop psu3800 24 v/40 a