Siemens SITOP PSU8200 24 V/20 A User Manual page 59

3ph
Hide thumbs Also See for SITOP PSU8200 24 V/20 A:
Table of Contents

Advertisement

Output
Rated voltage U
DC
out rated
Total tolerance, static ±
Static line regulation, approx. 0.1 %
Static load regulation,
approx.
Residual ripple in the load
range
Peak-peak, max.
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
Adjustment range
Output voltage can be
adjusted
Output voltage adjustment
Remark
Operating display
Signaling
Response when switching
on/off
Starting delay, max.
Voltage rise, typ.
Rise time of the output
voltage, max.
Rated current I
out rated
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
6EP3424-8UB00-0AY0
(12 V/20 A)
Regulated, isolated DC volt-
age
12 V
3 %
0.2%
100 mV
200 mV
12 - 14 V
Yes
Via potentiometer
max. 240 W
LED green for "12 V O.K."
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "12 V
O.K."
No overshoot of U
(soft
out
start)
2.5 s
150 ms
500 ms
20 A
6EP3436-8UB00-0AY0
(24 V/17 A)
Regulated, isolated DC volt-
age
24 V
3 %
0.1 %
0.2%
100 mV
200 mV
24 - 28 V
Yes
Via potentiometer
Max. 480 W
LED green for "24 V O.K."
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "24 V
O.K."
No overshoot of U
(soft
out
start)
2.5 s
150 ms
500 ms
17 A
Technical data
6.2 Output
6EP3437-8UB00-0AY0
(24 V/40 A)
Regulated, isolated DC volt-
age
24 V
3 %
0.1 %
0.2%
100 mV
200 mV
24 - 28 V
for U
< 360 V: 24 - 26 V
in
Yes
Via potentiometer
Max. 960 W
LED green for "24 V O.K."
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "24 V
O.K."
No overshoot of U
(soft
out
start)
2 s
150 ms
500 ms
30/40 A
59

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop psu8200 36 v/13 aSitop psu8200 48 v/10 aSitop psu8200 48 v/20 aSitop psu3800 24 v/17 aSitop psu3800 12 v/20 aSitop psu3800 24 v/40 a

Table of Contents