2.3

Potentiometer

The potentiometer
The output voltage is set to U
compensate voltage drops along long power supply cables up to the load.
Figure 2-4
NOTICE
Thermal overload possible
When adjusting the output voltage U
the permissible ambient temperature must be taken into account with 3 °C/V.
Note
It is only permissible to use an insulated screwdriver when actuating the potentiometer.
For notes on actuating the potentiometer (screwdriver, torque), see Figure 2-2 Terminal data
for 6EP3436-8SB00-0AY0, 6EP3446-8SB10-0AY0, 6EP3446-8SB00-0AY0, 6EP3424-
8UB00-0AY0 and 6EP3436-8UB00-0AY0 (Page 12) and Figure 2-3 Terminal data for
6EP3437-8SB00-0AY0, 6EP3447-8SB00-0AY0, 6EP1437-3BA10 and 6EP3437-8UB00-
0AY0 (Page 12)
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
at the front of the device is used to adjust the output voltage.
out rated
Potentiometer
Description, device design, dimension drawing
in the factory, and can be changed – for instance to
, the output current must be derated by 4 %/V, or
out rated
2.3 Potentiometer