Input current at rated input
voltage 500 V
Inrush current limiting
(25 °C), max.
I
t, max
2
Integrated input fuse
Protection in the line feeder
cable (IEC 898)
Figure 6-1
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
6EP3424-8UB00-0AY0
(12 V/20 A)
0.6 A
16 A
0.8 A
s
2
None
Required: 3-pole, coupled
miniature circuit breaker
6 - 16 A characteristic C or
circuit breaker 3RV2011-
1DA10 (setting 3 A) or
3RV2711-1DD10 (UL489-
listed, DIVQ)
Power failure buffering
6EP3436-8UB00-0AY0
(24 V/17 A)
0.9 A
16 A
0.8 A
s
2
None
required: 3-pole, coupled
miniature circuit breaker
6 - 16 A characteristic C or
circuit breaker 3RV2011-
1DA10 (setting 3 A) or
3RV2711-1DD10 (UL489-
listed, DIVQ)
Technical data
6.1 Input
6EP3437-8UB00-0AY0
(24 V/40 A)
2.1 A
15 A
2.3 A
s
2
None
required: 3-pole, coupled
miniature circuit breaker
10 - 16 A characteristic C or
circuit breaker RV2011-
1DA10 (setting 3 A) or
3RV2711-1DD10 (UL489-
listed, DIVQ)
55