Group 1; Enabled; Disabled; System Config - GE P50 Agile P253 Technical Manual

Motor protection relay
Table of Contents

Advertisement

5 Configuration
LIMIT NB STARTS
2.3.16.2
Group 1 –System Configuration Submenu
Edit Settings
2.3.16.2.1

GROUP 1

SYSTEM CONFIG

2nd Harmonic

Disabled

Edit Settings
2.3.16.2.2
GROUP 1
SYSTEM CONFIG
2nd Harmonic

Enabled

2nd Harm Thresh
20%
5-36
nd
(if 2
harmonic is disabled)
nd
(if 2
harmonic is enabled)
Password protected window for Limit NB Starts i.e. Hot Start Status
(Hot Start NB), Cold Start Stat (Cold Start NB), Supervising Time,
T.Betw.St.Status (Time Betwn Start), Inhib. Strt Time
Note: Setting will be seen only when it is enabled in Configuration
setting.
Password protected window for "GROUP 1'' setting:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Note: Group 1 settings will be seen only when it is enabled in
Configuration menu.
Password protected window for System Configuration i.e. 2nd
Harmonic (Disabled/Enabled), 2nd Harmonic Threshold and I>lift 2H.

Editable setting

By using the (+ /5) or (- /6) key, 2nd Harmonic set as Disabled.
Password protected window for "GROUP 1'' setting:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Note: Group 1 settings will be seen only when it is enabled in
Configuration menu.
Password Protected window for System Configuration i.e. 2nd
Harmonic (Disabled/Enabled), 2nd Harmonic Threshold and I>lift 2H.
Editable setting
By using the (+ /5) or (- /6) key, 2nd Harmonic is Enabled.
Editable setting
By using the (+ /5) or (- /6) key, the desired 2nd Harmonic
Threshold can be set. The setting range is 5% to 70% in steps of 1%.
P50 Agile P253
P253/EN M/C