13 Technical Specifications
Damped oscillatory
4.9
magnetic field
Damped oscillatory
4.10
test
Mechanical tests
5.
Vibration response
5.1
test
Vibration endurance
5.2
test
Shock response test
5.3
5.4
Shock endurance test
5.5
Bump test
5.6
Seismic test
13-10
EN61000-4-10:1993 +
Class 5: 100A/m field applied in all planes at 100kHz / 1MHz with burst duration of 2
A1:2001, Level 5
Sec.
1) 100kHz and 1MHz slow damped oscillatory applied in common mode at 2.5 KV
EN 61000-4-18: 2007 +
A1:2010
2) 3MHz, 10MHz, 30MHz fast damped oscillatory applied in common mode at 1 KV
Frequency range
Crossover frequency
Peak displacement before crossover
EN 60255-21-1:1996
Class 2
Peak acceleration after crossover
No. of sweep cycles per axis
EUT condition
Frequency range
Peak acceleration
EN 60255-21-1:1996
Class 2
No. of sweep cycles per axis
EUT condition
Peak acceleration
Pulse duration
EN 60255-21-2:1996
Class 2
No. of pulses in each direction
EUT condition
Peak acceleration
Pulse duration
EN 60255-21-2:1996
Class 2
No. of pulses in each direction
EUT condition
Peak acceleration
Pulse duration
EN 60255-21-2:1996
Class 2
No. of pulses in each direction
EUT condition
Frequency range
Crossover frequency
EN 60255-21-3:1995
Peak displacement before crossover X
(Class 2 - 2g peak)
Peak displacement before crossover Y
Peak acceleration after crossover X
P50 Agile P253
10 Hz to 150 Hz
58 to 60 Hz
0.075mm
1 gn
1
Energised
10 to 250Hz
2 gn
20
Non energised
10 gn
11 ms
5
Energised
30 gn
11 ms
3
Non energised
20 gn
16 ms
1000
Non energized
1 to 35 Hz
8 Hz
7.5 mm
3.5 mm
2 gn
P253/EN M/C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents