P50 Agile P253
LED R HR/SR
0000
ANDEQ A Op Time
0.05 S
ANDEQ A Rst Time
0.05 S
ANDEQ B Op Time
1 S
ANDEQ B Rst Time
1 S
ANDEQ C Op Time
1 S
ANDEQ C Rst Time
1 S
ANDEQ D Op Time
1 S
ANDEQ D Rst Time
1 S
P253/EN M/C
Editable setting
By using the (+ /5) or (- /6) key, the desired function for LED RED can
be set as HR/SR ('1'=HR /'0'=SR)
Editable setting
By using the (+ /5) or (- /6) key, the desired AND Equation A
Operation Time can be set. The setting range is from 1 to 3600s in
steps of 1s.
Editable setting
By using the (+ /5) or (- /6) key, the desired AND Equation A Reset
Time can be set. The setting range is from 1 to 3600s in steps of 1s.
Editable setting
By using the (+ /5) or (- /6) key, the desired AND Equation B
Operation Time can be set. The setting range is from 1 to 3600s in
steps of 1s.
Editable setting
By using the (+ /5) or (- /6) key, the desired AND Equation B Reset
Time can be set. The setting range is from 1 to 3600s in steps of 1s.
Editable setting
By using the (+ /5) or (- /6) key, the desired AND Equation C
Operation Time can be set The setting range is from 1 to 3600s in steps
of 1s.
Editable setting
By using the (+ /5) or (- /6) key, the desired AND Equation C Reset
Time can be set. The setting range is from 1 to 3600s in steps of 1s.
Editable setting
By using the (+ /5) or (- /6) key, the desired AND Equation D
Operation Time can be set. The setting range is from 1 to 3600s in
steps of 1s.
Editable setting
By using the (+ /5) or (- /6) key, the desired AND Equation D Reset
Time can be set. The setting range is from 1 to 3600s in steps of 1s.
5 Configuration
5-33