GE P50 Agile P253 Technical Manual page 187

Motor protection relay
Table of Contents

Advertisement

P50 Agile P253
Sr. No
This command allows the displayed settings to be copied to a selected setting group.
6.
This setting enables or disables settings Group 1. If the Setting Group 1 is enabled from the configuration setting, then all associated
settings and signals are available in Group 1 setting menu. If the Setting Group1 is disabled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
7.
This setting enables or disables settings Group 2. If the Setting Group 2 is enabled from the configuration setting, then all associated
settings and signals are available in Group 2 setting menu. If the Setting Group 2 is disabled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
8.
This setting hides or unhides the System Config menu. Inside the 2nd Harmonic blocking related parameters are present.
9.
This setting enables (activate) or disables (turn off) the Phase Over current Protection function. If disabled, then all associated settings
and signals are hidden, with the exception of this setting. Same for all other items
10.
This setting enables (activate) or disables (turn off) the Negative Sequence OC Protection.
11.
This setting enables (activate) or disables (turn off) the Measured Earth Fault Protection function
12.
This setting enables (activate) or disables (turn off) the Derived Earth Fault Protection function.
13.
This setting enables (activate) or disables (turn off) the Thermal Overload function.
14.
This setting enables (activate) or disables (turn off) the Loss of Load Protection.
15.
This setting enables (activate) or disables (turn off) the CB Fail Protection.
16.
This setting enables (activate) or disables (turn off) Stall Protection.
17.
This setting enables (activate) or disables (turn off) Number of Starts limitation Protection.
18.
This setting determines the full load current
19.
This setting determines the representation of Phases. Based on this setting, the representation in measurements, records etc shall
change. No change is expected for the stored records, if any
20.
This setting determines the reference for all settings dependent on the transformer ratios; either referenced to the primary or the
secondary.
2.5
TRANS. RATIOS Settings
Sr. No
1.
This setting specifies to enter the set password
2.
This setting determines the phase current transformer input primary current rating.
3.
P253/EN M/C
Parameter
Setting Group 1
Setting Group 2
System Config
Overcurrent
Neg Sequence O/C
Earth Fault 1
Earth Fault 2
Thermal Overload
Loss of Load
CB Fail
Stall Protection
Limit Nb Starts
IFL
Measure't Setup
Setting Values
Parameter
Password
0000
Phase CT Primary
100A
Phase CT Sec'y
1 A
Defaults setting
Enabled
Disabled
Disabled
Enabled
Disabled
Enabled
Enabled
Disabled
Disabled
Disable
Disabled
Disabled
1*ln
ABC
Secondary
Defaults setting
0000 to zzzz
1 to 30000A step 1A
1A or 5 A
7 Protection Parameter Settings
Setting/Ranges
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
0.2*In to 4*In step 0.01*In
ABC/RYB
Primary/Secondary
Setting/Ranges
7-7