13 Technical Specifications
2.
Auxiliary Supply tests
DC voltage dips
2.1
DC voltage
2.2
interruption
2.3
AC voltage dips
AC voltage
2.4
interruption
AC (ripple) in DC
2.5
supply
Gradual shutdown/
2.6
start-up test
Reversal of DC power
2.7
supply polarity test
3.
Emission tests
Radiated emission
3.1
test
Conducted emission
3.2
test
13-8
IEC 61000-4-29 Class A
Residual voltage
IEC60255-26(ed3.0)-
1) At 40% for 200ms. 2) At 70% for 500ms.
2013
1) DC auxiliary supply interruptions for 10, 20ms with no loss of protection.
IEC 61000-4-29 Class A
IEC60255-26(ed3.0)-
2) DC auxiliary supply interruptions 50ms, 100ms, 200ms, 0.5s, 5s with temporary
2013
loss of protection.
Residual voltage
IEC 61000-4-11 Class A
1) At 40% for 200ms. 2) At 70% for 500ms.
IEC60255-26(ed3.0)-
2013
3) At 80% for 5s.
IEC 61000-4-11 Class A
1) AC auxiliary supply interruptions for 10, 20ms with no loss of protection.
IEC60255-26(ed3.0)-
2) AC auxiliary supply interruptions for 50ms, 100ms, 200ms, 0.5s, 5s with
2013
temporary loss of protection.
IEC 60255-11,
Level: 15%
IEC60255-26(ed3.0)-
Frequency: 100 /120 Hz
2013
The unit must power down and up correctly with no mal operation.
IEC60255-26(ed3.0)-
Shut down time
2013
Power off time
Startup time
IEC 60255-11
Product shall withstand for 1 minute with Reverse polarity of power supply inputs.
The EUT shall satisfy the requirement of this specification.
Radiation measured at a distance of 10 meter.
EN55022:2006+A1:200
7
Frequency range
IEC60255-26(ed3.0)-
30 MHz – 230 MHz
2013
230 MHz – 1000 MHz
EUT condition
The EUT shall satisfy the requirement of this specification.
Frequency range
0.15 – 0.5 MHz
IEC60255-26(ed3.0)-
2013
0.5 – 30 MHz
EUT condition
P50 Agile P253
60s
5 min.
60s
Limits
40 dB (µV/m)
47 dB (µV/m)
Energised
Limits
79 dB/µV (Quasi peak)
66 dB/µV (Average)
73 dB/µV (Quasi peak)
60 dB/µV (Average)
Energised
P253/EN M/C