GE P50 Agile P253 Technical Manual page 289

Motor protection relay
Table of Contents

Advertisement

P50 Agile P253
4.
Immunity tests
High frequency
4.1
disturbance test
Electrostatic
4.2
discharge
4.3
Surge immunity test
Fast transient
4.4
Radiated radio
frequency
4.5
electromagnetic field
disturbance test
Conducted
disturbance inducted
4.6
by radio frequency
field
Power frequency
magnetic field
4.7
immunity
Pulsed magnetic field
4.8
immunity
P253/EN M/C
1) 2.5 kV Common mode
a) Between Independent circuit and case earth.
IEC 60255-22-1 and
b) Independent circuit.
IEC60255-26(ed3.0)-
2013
2) 1 kV Differential mode
a) Independent circuit.
EUT condition : Energised
1) 15kV air discharge
EN61000-4-2:2009
Level 3 and Level 4
2) 8kV contact discharge
IEC60255-26(ed3.0)-
3) 15kV indirect discharge
2013
EUT condition : Energised
1) 4KV: Power supply common mode
EN61000-4-5:2006
2) 2KV: Power supply differential mode
Level 4
3) 4KV: CT / input / output ports common mode
IEC60255-26(ed3.0)-
4) 2KV: CT / input / output ports differential mode
2013
EUT condition : Energised
EN 61000-4-4:2004 +
1) 4kV 5 kHz and 100 kHz, applied to all circuits excluding communication ports
A1:2010 Level 4.
2) 2kV 5 kHz and 100 kHz, applied to communication ports
IEC60255-26(ed3.0)-
EUT condition: Energised
2013
Voltage level
Frequency range
EN 61000-4-3:
2006+A1:2008 Level 4,
IEC60255-26(ed3.0)-
2013
Modulation
Spot frequency
Voltage level
Frequency range
EN 61000-4-6: 2009
Level 3
Modulation
IEC60255-26(ed3.0)-
2013
Dwell time
Spot Frequency
1) Class 5: 100A/m field applied continuously in all planes for the EUT in a quiescent
EN61000-4-8:2010
and tripping state
Level 5
2) Class 5: 1000A/m field applied for 3s in all planes for the EUT in a quiescent and
IEC60255-26(ed3.0)-
tripping state
2013
EUT condition : Energized
EN 61000-4- 9
Class 5: 1000A/m field applied continuously in all planes for the EUT in a quiescent
:1993+A1:2001, Level
and tripping state
5
13 Technical Specifications
For 10 V/m
For 30V/m
10 V/m and 30 V/m
800 – 1000 MHz , 1.4 – 2.7 GHz
80 – 960 MHz , 1.4 – 2 GHz
80% AM @ 1 KHz
80, 160, 380, 450, 900,1850 & 2150MHz
10 V
0.15 – 80 MHz
80% AM @ 1 KHz
2.85 Sec.
27, 68 MHz
13-9

Hide quick links:

Advertisement

Table of Contents
loading