GE P50 Agile P253 Technical Manual page 189

Motor protection relay
Table of Contents

Advertisement

P50 Agile P253
2.8
IO CONFIGURATION Settings
Sr. No
1.
This setting specifies to enter the set password
2.
This cell sets the output contact RL1 – RL6 for desired function.
3.
This cell sets the Green LED L5 – L8 for desired function.
4.
This cell sets the RED LED L5 – L8 for desired function.
5.
This cell sets the input for AND Logic equation (A, B, C and D).
6.
This cell sets the Opto I/P 1 – Opto I/P 6 for desired function.
*Note:
2.9
O/P RELAY CONFIG Settings
Sr. No
1.
This setting specifies to enter the set password
2.
This setting specifies the reset mechanism (manual/hand reset or self reset) for O/P relay contacts.
3.
4.
5.
6.
7.
8.
This setting specifies the time duration for which the output contacts holds its state after non availability of the command to the O/P
contact.
9.
This setting specifies the reset mechanism (manual/hand reset or self reset) for Green LED.
10.
This setting specifies the reset mechanism (manual/hand reset or self reset) for RED LED.
11.
12.
P253/EN M/C
Parameter
Password
0000
Relay
654321
Gen Strt*
000000
LED G
8765
Gen Strt*
0000
LED R
8765
Gen Strt*
0000
AND Logic
DCBA
Gen Strt*
0000
Opto I/P
654321
Rem.Rst*
000000
The functions which can be assigned to Output Relay, LED Green, LED RED, AND Logic
and Opto I/P are listed in Chapter 8: Monitoring and Control.
Parameter
Password
0000
Contact HR/SR
000000
O/P-1 Open Time
0.05 S
O/P-2 Open Time
0.05 S
O/P-3 Open Time
0.05 S
O/P-4 Open Time
0.05 S
O/P-5 Open Time
0.05 S
O/P-6 Open Time
0.05 S
LED G HR/SR
0000
LED R HR/SR
0000
ANDEQ A Op Time
1 S
ANDEQ A Rst Time
1 S
Defaults setting
0000 to zzzz
6 RL6........1RL1
1 = assigned ; 0 = not assigned
8 LED8........5LED5
1 = assigned ; 0 = not assigned
8 LED L8.....5LED L5
1 = assigned ; 0 = not assigned
D AND Logic D........A AND Logic A
1 = assigned ; 0 = not assigned
6 S6........1S1
1 = assigned ; 0 = not assigned
Defaults setting
0000 to zzzz
1= HR / 0 = SR
0s to 1s step of 0.01s
0s to 1s step of 0.01s
0s to 1s step of 0.01s
0s to 1s step of 0.01s
0s to 1s step of 0.01s
0s to 1s tep of 0.01s
1= HR / 0 = SR
1= HR / 0 = SR
1s to 3600s step of 1s
1s to 3600s step of 1s
7 Protection Parameter Settings
Setting/Ranges
Setting/Ranges
7-9