Input/Output Signals - Emerson Micro Motion 1500 Installation Manual

Hide thumbs Also See for Micro Motion 1500:
Table of Contents

Advertisement

Specifications
7.2

Input/output signals

Table 7-2:
Description
One active 4–20 mA output, not intrinsically safe:
Isolated to ±50 VDC from all other outputs and Earth ground
Maximum load limit: 820 ohms
Can report mass flow or volume flow
Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE43 Version 03.02.2003
One active frequency/pulse output, not intrinsically safe:
Can report mass flow or volume flow, which can be used to indicate flow rate or total
Reports the same flow variable as the mA output
Scalable to 10,000 Hz
Voltage is +15 VDC ±3% with 2.2 kohm internal pull-up resistor
Linear with flow rate to 12,500 Hz
Configurable polarity: active high or active low
Can be configured as a discrete output to report five discrete events, flow direction, flow
switch, calibration in progress, or fault
Service port, Modbus/RS-485 (terminals 33-34)
After device power up, terminals 33 and 34 are available in service port mode for 10 seconds:
-
-
-
-
-
After 10 seconds, terminals 33 and 34 default to Modbus/RS-485:
-
-
-
-
HART/Bell 202:
HART Bell 202 signal is superimposed on the primary milliamp output, and is available for host
system interface. Frequency 1.2 and 2.2 kHz, Amplitude: to 1.0 mA, 1200 baud, Requires 250
to 600 ohms load resistance
HART revision 5 as default, selectable to HART revision 7
One zero button that can be used to start the flowmeter zeroing procedure
48
I/O and digital communication for Model 1500 transmitters
Modbus RTU protocol
38,400 baud
No parity
One stop bit
Address = 111
Modbus RTU or Modbus ASCII protocol (default: Modbus RTU)
1200 to 38,400 baud rate (default: 9600)
Stop bit configurable (default: one stop bit)
Parity configurable (default: odd parity)