Weight
Electrical
Cooling Water
NOTE: Water conditioning may be required for applications not meeting these requirements.
©2007 Helix Technology Corporation
The weight of the Compressor is listed in
Table 1-1: Compressor Weight
The electrical specifications of the Compressor are listed in
Table 1-2: Electrical Input Specifications
Parameter
Operating Voltage Range/Frequency
Phase
Nominal Input Power
Nominal Power Factor
Rated FL/LR* Current
Minimum Electrical Service
*FL/LR = Full Load/Locked Rotor
The water used to cool the Compressor must meet the specifications shown
in
Table 1-3
for proper system operation.
Table 1-3: Cooling Water Specifications
Parameter
Maximum Inlet Temperature
Minimum Inlet Temperature
Flow Rate
Part Number 8040437, Revision 104, 06/12/2007, ECO Number 18068
Weight lbs./kg
267/121kg
342-457V/50 Hz
342-506V/60 Hz
5.5 KW/60 Hz
2.75 ±1.25 gpm (10.4 ± 4.7 lpm)
Table
1-1.
Table
Value
3
5KW/50 Hz
0.85
8/40
15 Amps
Value
90°F (32°C)
50°F (10°C)
1-2.
1-5