Electrical Installation - Culligan CSM Series Installation, Operating And Service Instructions

Commercial filters
Table of Contents

Advertisement

Figure 33.

Electrical Installation

CAUTION!
Observe the precautions listed below before electrical installation of your MVP control-
ler. Failure to do so may cause permanent damage to the controller.
Follow the local electrical code requirements.
Be sure electrical power is off and disconnected at the source before completing any wiring/cabling connections.
Provide a dedicated 120-volt circuit for the MVP system to ensure maximum electrical protection.
DO NOT include the MVP wiring cables in any conduit or raceway containing other 120-volt or higher circuits.
Maintain a distance of at least 10 feet between the MVP controller and any electrical distribution panels, raceways
carrying 300 volts or more, and electrical motors of 1 horsepower or more.
Use the cabling provided. Failure to do so may effect performance of the MVP controller adversely.
NOTE
One transformer is required for each controller in the system. Do not attempt to operate multiple con-
trollers without a dedicated transformer for each or your system will experience operational difficul-
ties.
22
Culligan® CSM Series Filters
6
2
5
DR
ALTERNATING/PROGRESSIVE FLOW PARALLEL SYSTEM W/PLUGGED BYPASS
IN
1
3/4
Brunermatic
Valve
22
Cat. No. 01016449