Culligan CSM Series Installation, Operating And Service Instructions page 58

Commercial filters
Table of Contents

Advertisement

Problem or Symptom
MVP Control Display
Error ERR1
(The control will not function while an
Error is displayed or detected.)
To clear an alarm condition after
correction, press and hold the Sta-
tus key for 10 seconds. The control
will then cycle the valve to the home
position.
You may also power down the con-
trol for 60 seconds or toggle a DIP
switch. If the problem is still pres-
ent after attempting to clear the er-
ror code, the code will remain in the
display.
MVP Control Display
Error ERR2
To clear an alarm condition after cor-
rection, press and hold the Status
key for 10 seconds. The control will
then cycle the valve to the home
position.
You may also power down the con-
trol for 60 seconds or toggle a DIP
switch. If the problem is still pres-
ent after attempting to clear the er-
ror code, the code will remain in the
display.
MVP Control Display
Error ERR3
To clear an alarm condition after cor-
rection, press and hold the Status
key for 10 seconds. The control will
then cycle the valve to the home
position.
You may also power down the con-
trol for 60 seconds or toggle a DIP
switch. If the problem is still pres-
ent after attempting to clear the er-
ror code, the code will remain in the
display.
MVP Control Display
Error ERR4
To clear an alarm condition after cor-
rection, press and hold the Status
key for 10 seconds. The control will
then cycle the valve to the home
position. You may also power down
the control for 60 seconds or toggle
a DIP switch. If the problem is still
present after attempting to clear the
error code, the code will remain in
the display.
54
Culligan® CSM Series Filters
Error
Mode of Detection
Description
Motor Failure to
The error will occur if the valve
Start
fails to reach the desired state
within 70 seconds of driving the
motor. The control will attempt
to start the motor 3 times for 70
seconds each time with a 60-sec-
ond off period between each
attempt.The control will power
down all triacs until the problem
is corrected. The control beeper
will sound 3 times per second
every 30 seconds until any key is
pressed.
Motor Failure to
If the control detects changes in
Stop
the cam inputs when the motor is
not supposed to be turning.
Incorrect Cycle
The control expects to be in a dif-
Position
ferent position than that indicated
by the cam switch closures.
Units Have the
The error occurs when multiple
Same ID
units are connected and an ID
number is shared between mul-
tiple controls.
Possible Cause/Remedies
Poor motor - Replace
Bad Cam - Inspect/Replace.
Bad/loose wiring-Inspect/
Repair.
Problem with MVP circuit
board - run Test program
to verify operation of board
components.
Pilot spool is bound, pro-
hibiting motor from moving-
Inspect/Repair.
Micro-switches not function-
ing/sticking -Inspect/Replace
Poor motor - Replace
Problem with MVP circuit
board - run Test program
to verify operation of board
components.
Micro-switches not function-
ing/sticking -Inspect/Replace.
Poor motor - Replace
Bad Cam - Inspect/Replace.
Bad/loose wiring - Inspect/
Repair.
Problem with MVP circuit
board - run Test program
to verify operation of board
components.
Pilot spool is bound, prohibit-
ing motor from moving. -
Inspect/Repair.
Micro-switches not function-
ing/sticking -Inspect/Replace.
Refer to
page 35
and the sec-
tion on Multiple Unit Communica-
tion Setup and re-establish ID's.