Xinje XC series Hardware Manual page 37

8 channels analog input (14bit): 4 channels current input, 4 channels voltage input. 4 channels analog input (14bit); 2 channels analog output (12bit): current / voltage selectable. 4 channels analog output (12bit): current / voltage selectable. -150 t
Hide thumbs Also See for XC series:
Table of Contents

Advertisement

6-1 Programming
Item
Analog input signal
Temperature testing
range
Digital output range
Control precision
Resolution
Integral precision
Conversion speed
Analog power usage
Install format
External size
Note
Without signal input, the channel's data is 3500.
XC series analog expansions User Manual Page 37 of 53
Content
Pt100 platinum thermo-resistance
-100 to 350 ºC
-1000 to 3500 16 bits with sign bit, binary
±0.5 ºC
0.1 ºC
±0.8% relative to the max value
100ms×6 channels
DC24V±10% 50mA
Fixed with M3 screws or directly installed on DIN rail
63mm × 102mm × 73.3mm
Characteristic
Platinum thermo-resistance
input, Pt100
6 channels input, 6 channels
output
2 groups PID parameters
(every 3 channels has a
group of PID parameters)
Resolution is 0.1ºC
Up to 7 modules can be
installed