Xinje XC series Hardware Manual page 21

8 channels analog input (14bit): 4 channels current input, 4 channels voltage input. 4 channels analog input (14bit); 2 channels analog output (12bit): current / voltage selectable. 4 channels analog output (12bit): current / voltage selectable. -150 t
Hide thumbs Also See for XC series:
Table of Contents

Advertisement

Items
Analog input
range
Max input range
Analog output
range
Digital input
range
Digital output
range
Bit range
PID control
value
Resolution
Conversion
speed
Power usage
Install format
External size
XC series analog expansions User Manual Page 21 of 53
Analog input (AD)
Voltage input
Current input
DC 0-5V / 010V
DC 0/20mA,
4/20mA
DC±18V
DC 0 / 40mA
-
-
14 bits binary data, 0 - 16,383
1/16383(14Bit); the converted data is
stored into PLC in the format of HEX
format (14Bit)
0~4095
0.8%
15ms per channel
DC24V±10%,100mA
Fixed with M3 screws or directly installed on DIN rail
63mm × 102mm × 73.3mm
Analog output (DA)
Voltage output
Current output
-
-
DC: 0-5V / 0-10V
DC: 0-20mA /
4-20mA
(Exterior load
(Exterior load
resistance is
resistance
2KΩ~1MΩ)
less than
500Ω)
12 bits binary data, 0-4095
-
1/4095(12Bit) the converted data
is stored into PLC with the format
of HEX. (12Bit)
-
2ms per channel
MANU003R2V1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc-e8adXc-e6tc-pXc-e4daXc-e4ad2daXc-e6pt-p

Table of Contents